Relay Basics (Under Field *80) - ADEMCO Via 30+ Installation Instructions Manual

Table of Contents

Advertisement

OUTPUT AND
*80
OUTPUT
RELAYS
SYSTEM
SETUP
Applicable only if field *25 is programmed for a 4229 or 4204...otherwise
(*80-*92)
skip this field.
REFER TO THE OUTPUT RELAY TABLE FOR THIS FIELD
IN THE PROGRAMMING FORM.
Relay Basics
Relays can be used to perform many different functions and actions. In this sys-
tem, each relay must be programmed as to how to act (ACTION), when to activate
(START), and when to deactivate (STOP). Each of these is summarized briefly
below, but described later in detail in the programming procedure for fields *80
and *81.
1.
ACTION: The "ACTION" of the relay is how the relay will respond when it is
activated by the "START" programming. There are 4 different choices of
actions:
¢ CLOSE for 2 SECONDS and then reset.
* CLOSE and STAY CLOSED until deactivated by "STOP" programming.
¢ PULSE ON and OFF until deactivated by "STOP" programming.
«NO RESPONSE is chosen when the relay is not used.
2.
START: The "START" programming instructs the relay when and under
what conditions to activate. There are 3 parts to be programmed:
* EVENT instructs the relay what condition must occur to the zone(s) pro-
grammed into the "ZONE LIST" in order to activate the relay. The
"EVENT" and "ZONE LIST" work together. The 4 different choices for
"EVENT" are listed in the PROGRAMMING section for field *80.
e ZONE LIST is a list of zones selected by the installer in field *81.When an
event occurs as assigned by "EVENT" on any zone within that list, the
relay will activate as selected in "ACTION". In this way, many zones can
be assigned very easily to a single event. For example: You may wish
a relay to activate (perhaps to activate a strobe for a visual indication)
whenever any zone in a group of zones is faulted.
* ZONE TYPE/SYSTEM OPERATION. Instead of using a "ZONE LIST" and
"EVENT", a specific zone (response) type or system operation action
can be selected to activate the relay.
If a specific
"ZONE
TYPE"
is chosen,
any zone
of that re-
sponse type going into alarm, trouble, or fault will cause the relay to ac-
tivate as selected in "ACTION".
If a "SYSTEM
OPERATION"
is chosen, that operation will cause
the relay to activate as selected in "ACTION".
The different choices for "ZONE TYPE" and "SYSTEM OPERATION"
are listed in the PROGRAMMING section for field *80.
3.
STOP: The "STOP" programming instructs the relay when and under what
conditions to deactivate. The 2 parts to be programmed are:
e RESTORE ZONE LIST. If a "RESTORE ZONE LIST" is used, the relay will
deactivate when all the zones in that list restore from a previous fault of
alarm condition. This will occur regardless of what is programmed to
"START" the relay; therefore,
a "RESTORE ZONE LIST" would nor-
mally only be used when a "ZONE LIST" is used to start the relay.
« ZONE TYPE/SYSTEM
OPERATION.
Instead of using
a "RESTORE
ZONE LIST", a specific zone (response) type or system operation ac-
tion can be selected to deactivate the relay.
If a specific
"ZONE
TYPE"
is chosen,
any zone
of that re-
sponse type that restores from a previous alarm, trouble, or fault condi-
tion will cause the relay to deactivate.
if a "SYSTEM
OPERATION"
is chosen, that operation will cause
the relay to deactivate.
The different choices for "ZONE TYPE" and "SYSTEM OPERATION"
are listed in the PROGRAMMING section for field *80.
-24-

Advertisement

Table of Contents
loading

Table of Contents