ADEMCO VIA-30Pse Installation Instructions Manual

Hide thumbs Also See for VIA-30Pse:
Table of Contents

Advertisement

Security System

VIA-30P
SE
THIS ISSUE INCLUDES THE NEW QED (QUICK ENROLLLMENT
OF DEVICES) PROCEDURE FOR 5800 SERIES TRANSMITTERS
Installation Instructions • Installation Instructions • Installation Instructions
WWW.DIYALARMFORUM.COM
N7225V2 4/97

Advertisement

Table of Contents
loading

Summary of Contents for ADEMCO VIA-30Pse

  • Page 1: Security System

    Security System VIA-30P THIS ISSUE INCLUDES THE NEW QED (QUICK ENROLLLMENT OF DEVICES) PROCEDURE FOR 5800 SERIES TRANSMITTERS Installation Instructions • Installation Instructions • Installation Instructions WWW.DIYALARMFORUM.COM N7225V2 4/97...
  • Page 2: Recommendations For Proper Protection

    RECOMMENDATIONS FOR PROPER PROTECTION The following recommendations for the location of fire and burglary detection devices help provide proper coverage for the protected premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS Section 1. GENERAL DESCRIPTION ..................1-1 Section 2. INSTALLING THE CONTROL .................. 2-1 Mounting the Cabinet ..................... 2-1 Installing the Lock (if used) .................... 2-1 Installing the Control's Circuit Board Alone or (if used) With a 4204, 4219, or 4229 Module................2-1 Installing Control and RF Receiver Circuit Boards Together in the Cabinet....
  • Page 4 Section 6. WIRELESS (RF) ZONE EXPANSION (5700 & 5800 RF SYSTEMS), CONT'D 5800 Series Transmitter Setup ..................6-10 5800 Series Transmitter Input Loops ..............6-10 5800 Series Transmitter Input Types ..............6-10 Compatible 5800 Series Transmitters ................6-11 Programming the RF Transmitters (5800 RF Systems) ..........
  • Page 5 Section 13. ALPHA DESCRIPTOR PROGRAMMING ............. 13-1 Assigning Zone Descriptors..................13-1 Entering Zone Descriptors (in program Menu Mode 82) ........13-1 Programming the Descriptors ................13-1 Alternate Method for Programming Zone Descriptors ..........13-3 Adding Custom Words....................13-4 Alpha Vocabulary List (For Entering Zone Descriptors) ..........13-5 Character (ASCII) Chart ....................
  • Page 6 Figure 15. Connection of AAV Unit When Not Using a 4285 Phone module ..... 11-2 Figure 16. Connection of AAV Unit When Also Using a 4285 Phone module.... 12-2 Figure 17. VIA-30PSE Summary of Connections Diagram ....Inside Back Cover WWW.DIYALARMFORUM.COM...
  • Page 7: How To Use This Manual

    “Data Field Descriptions” in the separate PROGRAMMING GUIDE that has been supplied. If you are an experienced user of Ademco products, you may choose to wire and then program the entire system at one time. If so, refer to “Mechanics of Programming”...
  • Page 8: Conventions Used In This Manual

    (00 = Quit) When programming the system, data fields are indicated by a “star” [ ] followed by the data field number. PRODUCT MODEL NUMBERS: Unless noted otherwise, references to specific model numbers represent Ademco products. WWW.DIYALARMFORUM.COM...
  • Page 9: Section 1. General Description

    Section 1. GENERAL DESCRIPTION The VIA-30PSE is a control that supports up to 32 zones, using basic hardwired, wired expansion, and/or wireless, plus remote keypads. Basic Hardwired Zones (5 and 6) Provides 2 basic hardwired zones having the following characteristics: •...
  • Page 10 • The system can be uploaded, downloaded, or controlled via an IBM compatible computer, using either Ademco's V-Link downloading software (Rev. 4 or higher) or Ademco's Compass Windows downloading software, and a modem specified by Ademco. Keypad programming consists of: •...
  • Page 11: Section 2. Installing The Control

    LED in the receiver after it is operational). Random flicker is OK. Installing the Lock (if used) Use an Ademco No. N6277 Cam Lock and No. N6277–1 Push-On Clip (Retainer Clip). Note: The cabinet can be closed and secured without a lock by using 2 screws in the cover's edge.
  • Page 12 4204, 4219, or 4229/ 1. Insert self-tapping screws (provided) in two adjacent raised cabinet tabs. Leave the heads projecting 1/8". Expansion Unit 2. Hang the unit on the screw heads via two of the slotted holes at the rear of (if installed in cabinet) its housing, as shown in Figure 2.
  • Page 13: Installing Control And Rf Receiver Circuit Boards Together In The Cabinet

    Installing the Control and RF Receiver Circuit Boards Together in the Cabinet 1. Hang two short (black) mounting clips (provided with receiver) on the raised cabinet tabs, as shown in Detail B in Figure 3. 2. Insert the top of the receiver board (removed from its own case as de- scribed in its instruc tions) into the slots at the top of the cabinet, as shown in Detail A in Figure 3.
  • Page 14: Wiring The Ac Transformer

    Wiring The AC Transformer No. 1321 Wire the No. 1321 transformer to terminals 1 and 2 on the control board. See wiring table below for wire gauge to use. WIRING TABLE Distance of Transformer Wire Gauge From the Control Panel To Use Up to 50 feet # 20...
  • Page 15: Section 3. Installing Remote Keypads

    Section 3. INSTALLING REMOTE KEYPADS This section lists the wired keypads that may be used and provides instructions for wiring and mounting the keypads. A preliminary check-out procedure is also provided to ensure that the connected keypads are functioning properly in the system. Keypads That May Be Used •...
  • Page 16: Mounting The Keypads

    KEYPAD CONNECTOR CABLE ↓ BLACK KEYPADS GREEN YELLOW CONTROL TERMINALS Figure 5. Keypad Connections To The Control Board Mounting the Keypads 1. Make sure addressable type keypads (4137AD, 5137AD, 6128, 6137, 6138, and 6139) are set to non-addressable mode (address 31), which is the factory default setting.
  • Page 17: Preliminary Check-Out Procedure

    SUPPLEMENTARY CONTROL POWER SUPPLY TERMINAL STRIP – AUX AUX. DATA DATA – IMPORTANT: MAKE THESE CONNECTIONS DIRECTLY TO SCREW TERMINALS AS SHOWN. Figure 6. Using A Supplementary Power Supply For Keypads Preliminary Check-out Procedure If you want to check that the system is working before connecting field wiring from zones and devices, do the following: 1.
  • Page 18 WWW.DIYALARMFORUM.COM 3 –4...
  • Page 19: Basic Hard-Wired Zones 5 And 6

    Section 4. BASIC HARD-WIRED ZONES 5 AND 6 This section provides general information for the hard-wired zones in the system, plus specific instructions for installing 4-wire smoke/combustion detectors. Also included is a procedure for programming the hard-wired zones. Installing the Hard-Wired Zones Common Characteristics for Zones 5 and 6 •...
  • Page 20: Programming Hard-Wired Zones

    Compatible System Sensor 4-Wire Smoke/Combustion Detectors 1412 4-wire ionization products of combustion detector. 2412 4-wire photoelectric smoke detector. 2412TH 4-wire photoelectric smoke detector w/135°F (57°C) heat detector. A77–716B EOL relay module (supervisory module for wired 4-wire fire zone). 2112/24T Low-profile 4-wire photoelectric smoke detector w/135°F (57°C) heat detector.
  • Page 21: Programming Panic Keys

    Zone Types 00 = Zone Not Used 08 = 24 Hr Aux 01 = Entry/Exit #1 09 = Fire 02 = Not used 10 = Interior w/Delay 03 = Perimeter 20 = Arm Stay 5800 04 = Interior Follower 21 = Arm-Away 05 = Trouble Day/Alarm Night 22 = Disarm Systems...
  • Page 22: Check-Out Procedure For Hard-Wired Zones 5 And 6

    When you have programmed all the hard-wired zones and Panic keys satisfactorily, exit 56 interactive mode at the Enter Zn Num. prompt by entering [ 0] [0] as the next zone number. Then exit the programming mode by keying 99. See the special notes below, then proceed to the check-out procedure that follows.
  • Page 23: Wired Zone Expansion (4219, 4229)

    Section 5. WIRED ZONE EXPANSION This section provides information regarding the use of expansion modules (4219 or 4229) for expanding the number of wired zones in the system, describes the modules that can be used and their wiring connections, plus a procedure for programming the wired expansion zones. Installing Zone Expansion Units You can add an additional 8 wired expansion EOLR zones to the basic control's 8 hardwired zones, for a total of 14 wired zones, by using a No.
  • Page 24: Programming Wired Expansion Zones

    Programming Wired Expansion Zones 1. With at least one 2-line Alpha keypad (6139) connected to the keypad terminals on the control, power up the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system.
  • Page 25: Check-Out Procedure For Wired Expansion Zones

    At the “INPUT DEVICE” prompt, enter “2” (AUX 10 Input Dev: Wired) as the input device. The display on the AUX WIRED AW: 01 left will appear. Press [ ] to continue. Typical summary display A summary display will appear, showing the Zn ZT RC In data for the zone that was just programmed.
  • Page 26 3. Fault and restore every contact or sensor in each expansion zone individually to ensure that it is being monitored by the system. Each time a zone is faulted, the keypad should display the number of the faulted zone (as programmed by you just previously in 56 mode). When each zone is restored, the READY TO ARM message should appear again.
  • Page 27: Wireless Systems Available

    Wireless may not be used in UL Commercial Burglary installations. Wireless Systems Available The VIA-30PSE supports wireless zones which may be used exclusively, or in addition to hardwire zones 5 and 6. The system supports two different wireless systems which have many similarities, but notable differences in the programming of the transmitters for each system.
  • Page 28: Transmitter Battery Life

    The supervision for a particular transmitter in the 5800 system may be turned off by entering it as a "UR" (unsupervised RF) type, as described later. 5800 series transmitters have built-in tamper protection and will cause a “CHECK” condition to be annunciated if covers are removed. Each transmitter is also supervised for low battery and will transmit a low battery signal to its receiver, with the battery having at least 30 days of life re- maining.
  • Page 29: Installing The 5800Tm Module

    Terminal 7 BLUE: Not Used Do not cut any of the jumpers on the 5800TM when using it with the VIA-30PSE. For additional information, refer to the 5800TM’s instructions. 5700 Series Transmitter Setup Each 5700 series transmitter has DIP switches to set both the transmitter's zone number (Transmitter zone/ID) and the system House ID.
  • Page 30: Wireless Zone/Id Assignments For 5700 Series Transmitters

    Setting the DIP Switches Set the DIP switches on each 5700 series transmitter to the appropriate on 5700 Series zone/ID number and House ID. Refer to the Compatible 5700 Series Transmitters Transmitters table on a following page in this section for zone numbers and programming information for each particular transmitter.
  • Page 31: Dip Switch Tables For 5700 Rf System Wireless Devices

    DIP SWITCH TABLES FOR 5700 RF SYSTEM WIRELESS DEVICES 5775 PIR HOUSE ID 5701 PANIC TRANSMITTER 5706/5707 SMOKE DETECTOR/TRANSMITTER SWITCH SETTING FOR ALL DETECTORTRANSMITTER DEVICES EXCEPT 5716 MIRROR HOUSE ID (1 SHOWN) DIP SWITCH POSITION DEVICE SIDE 1 2 3 4 5 6 VIEW (UP) —...
  • Page 32: Compatible 5700 Series Transmitters

    Compatible 5700 Series Transmitters Model Product Zone/ID # Description 5701 Panic Transmitter 62 or 63 • Programmable for either silent or audible 24-hour alarm. 5706 Photoelectric Smoke 48–55 • One-piece smoke detector with Detector built-in transmitter. • Built-in UL Listed 85dB piezo electric alarm sounder and audible low battery warning.
  • Page 33: Programming The Control For A 5700 Wireless System

    Programming the Control For a 5700 Wireless System 1. With at least one two-line Alpha keypad wired and set to address 31 (default), power up the system temporarily by plugging the AC transformer (previously wired to the control) into a 120VAC outlet. 2.
  • Page 34 Data field 22 RF SYSTEM TYPE, must have been programmed for a 5700 RF system (“1”). Also, the House ID should have been entered in field 24, and all 5700 transmitters set to the same House ID. 4. Press 56. (Zone Programming Mode) Use this mode to program zone numbers, zone types, and alarm report codes for all 5700 wireless zones that are going to be used in the system.
  • Page 35: Go/Nogo Test

    10. Mark the zone number on the transmitter. 11. After the transmitter has been entered into the system, press [ ] to continue. Typical summary display A summary of the programmed values for the Zn ZT – RC In: selected zone will now be displayed 20 03 –...
  • Page 36: 5800 Series Transmitter Setup

    3. Mount the transmitter according to the instructions provided with the transmitter. 4. Exit the GO/NO GO test mode by entering Installer Code + (OFF ). You should now proceed to “Check-Out Procedure for Wireless Zones” at the end of this section. 5800 Series Transmitter Setup General 5800 series transmitters have built-in serial numbers that must be enrolled in...
  • Page 37: Compatible 5800 Series Transmitters

    Compatible 5800 Series Transmitters Enter As Input Model Product Device Type Description 5801 Wireless Panic UR or RF • Has four pushbuttons, each with a Transmitter unique input (loop) code. • Programmable responses (e.g., Panic, Arm–Stay, Arm–Away, Disarm, etc. 5802 Pendant BR Only •...
  • Page 38: Programming The Rf Transmitters (5800 Rf Systems)

    Compatible 5800 Series Transmitters (Continued) Enter As Input Model Product Device Type Description 5819 Shock Processor • Connects to externally mounted Transmitter inertia-type shock detector (not supplied). • Has built-in tampered cover switch. • Has 3 unique input (loop) codes: Loop 1: Terminals for a wired, N.C.
  • Page 39: Enrolling 5800 Transmitters Into The System

    Enrolling 5800 Transmitters Into The System There are two methods that may be used to enroll transmitters. The first method is performed in 56 zone programming mode (which is contained in this section) and describes how to enroll each transmitter into the system as you are entering the zone information. The second method is called "sequential mode"...
  • Page 40 ↓ Zone Number 6. Each zone must be assigned a zone type, which defines the way in 1 0 Zo n e T ype which the system responds to faults in that zone. Enter the zone type P e r im e te r desired (or change it, if necessary).
  • Page 41 The system will enroll the serial number of the first transmitter heard, 10 Input S/N: add the loop number entered to this serial number, display the serial A002-4064 and loop numbers, and cause the keypad to beep twice. If the serial and loop number combination is already present in the system, a single long beep will be heard from the keypad.
  • Page 42: (5800 System)

    (5800 System) Temporarily Or Permanently Removing A Zone From The System 1. Enter the programming mode: Key Installer Code + 8 + 0 and press [ ][5][6]. 2. Enter the zone number and press [ ]. A summary display will appear. 3.
  • Page 43 Go/No Go Test Before mounting transmitters permanently, conduct Go/No Go tests to verify (5700/5800 adequate signal strength and reorient or relocate transmitters if necessary. RF Systems) During this mode, wireless receiver gain is reduced by 50%. Testing in this mode assists in determining good mounting locations for the transmitters and verifies that the RF transmission has sufficient signal amplitude margin for the installed system.
  • Page 44 WWW.DIYALARMFORUM.COM 6 –18...
  • Page 45: Relay Device Basics

    Section 7. RELAY OUTPUT DEVICES Relay Device Basics Relays are programmable switches that can be used to perform many different functions. They can be used to turn lights on and off, control sounders, or for status indications. In this system, each relay must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP).
  • Page 46: Programming Options Defined

    4229 4229 RELAY DIP SWITCH RELAY CONNECTOR FOR SETTING ADDRESS AND ZONE “A” RESPONSE EITHER OR BOTH CAN BE USED TERMINALS ON RELAY CONTROL PANEL NO C NC 4-PIN CONSOLE PLUG GRN DATA OUT (TERM 6) TAMPER JUMPER POSITION TO CONTROL 4229 IN CABINET (–) GROUND (TERM 4)
  • Page 47 ZONE LIST (ZL) is a group of zones to which the “EVENT” applies in order to activate a particular relay. Note that there are a total of 3 zone lists that can be programmed in field 81 mode; when the selected EVENT (Alarm, Fault or Trouble) occurs in any zone in the selected “Start”...
  • Page 48: Programming Output Relays

    If a relay is energized before a 4-wire smoke detector is reset, the relay will be stopped by the interruption of Aux. Power that resets the smoke detector. If this is not desired, the power to the relay unit should be supplied from another 12V power source (e.g., the same source that is powering ex- ternal equipment through the relay contacts).
  • Page 49: Example Of Output Relay Programming

    If a zone type or system operation will be used to START the relay action, 02 Start: Zn Typ enter the appropriate two-digit code (see table that follows). If not, enter 00. Not Used Press the [ ] key to continue. CHOICES FOR ZONE TYPES 00 = Not Used 05 = Trouble Day/Alarm Night 08 = 24 Hr Aux...
  • Page 50 Press 81. (Zone Lists for Output Relays). This interactive mode is applicable only if you have programmed 80 mode. Refer to the Programming Form worksheet for 81 Mode. ↓ Zone List Displays Upon keying 81, this screen will appear. Enter the Zone List Number 01, 02, Zone List No.
  • Page 51: 4285 Phone Module

    Phone module and for programming the system for phone access via the Phone module. Installing the Phone module General The 4285 Phone module is an add-on accessory for the VIA-30PSE that Information permits access to the security system via a Touch-tone phone (either on premises or by a call-in when away).
  • Page 52: Caller Id Units

    1. Make 12V (+) and (–) and data in and data out connections from the Phone module to the control, using the connector cable supplied with the Phone module (see Figure 12). These are the same connections Color Lead Terminal On Control * as those used for remote GREEN DATA IN (terminal 6)
  • Page 53: Figure 12. 4285 Phone Module Wiring Connections

    4285 WIRING NOTES: 1. Wire the 4285 Phone module exactly as shown, using a direct-connect cord and RJ31X jack. 2. If Touch-tones are not heard when pressing keys following phone access to the security system via an on-premises phone , try reversing the pair of wires connected to terminals 3 & 4 on the 4285, and the pair of wires connected to terminals 17 &...
  • Page 54: Programming The Control For Phone Access

    Programming The Control For Phone Access 1. With at least one addressable keypad (but set to the non-addressable mode, address 31) connected to the keypad terminals on the control, power up the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system.
  • Page 55: Checking The Operation Of The 4285 Phone Module

    Checking the Operation of the 4285 Phone module To Check Phone Module Operation From an On-Premises Phone 1. Pick up phone and enter the programmed 2-digit phone code (entered in field . Annunciation of a VOICE (PHONE) MODULE ACCESS CODE) system status report should automatically start.
  • Page 56 WWW.DIYALARMFORUM.COM 8 –6...
  • Page 57: External Sounders

    This section provides a list of compatible sounders, connection information for an external sounder and programming procedures for those options that affect the operation of external sounders. Compatible Sounders Ademco AB-12M 10” Motor bell & box. UL Grade A. 100mA current Motorized Bell & Box draw.
  • Page 58: Sounder Connections

    3 pulses – pause – 3 pulses – pause – 3 pulses. . . repeated. Sounder Connections The VIA-30PSE provides a 12 VDC output which can power external alarm sounders (bells or sirens, see compatible sounders listed previously). This output will activate a sounder when an alarm occurs.
  • Page 59: Long Range Radio

    Section 10. LONG RANGE RADIO General Information Check availability of Model 7720PLUS or 7820 long range radio. If output to long range radio is selected, all messages that are programmed to go to the primary telephone line receiver will also be sent to the 7720PLUS or 7820 long range radio.
  • Page 60 WWW.DIYALARMFORUM.COM 10 – 2...
  • Page 61: Audio Alarm Verification (Aav) Unit

    Section 11. AUDIO ALARM VERIFICATION (AAV) UNIT General Information An Audio Alarm Verification (AAV) module, such as the Eagle 1241, is an add- on accessory that permits voice dialog between an operator at a central station and a person at the alarm installation, for the purpose of alarm verification. Alarm reports must be programmed for the primary phone number to enable this feature.
  • Page 62: Figure 15. Connection Of Aav Unit When Not Using A 4285 Phone Module

    INCOMING TELCO LINE DIRECT CONNECT CORD RJ31X RING PREMISES JACK ANSWERING MACHINE AND PLUG PHONES ANSWERING TERMINALS MACHINE 17 18 ON CONTROL EARTH GROUND REFER TO AAV MODULE INSTRUCTIONS FOR CONNEC- TIONS TO AUDIO SPEAKERS AND MICROPHONE INPUT TRIGGER RING 4204 MODULE NOTE:...
  • Page 63: Final Power Up

    Section 12. FINAL POWER UP In previous sections, you made temporary power connections for the purpose of programming and testing. This section provides information about final power-up procedures and battery size calculations. Earth Ground Connections The designated earth ground terminal (21) must be terminated in a good earth ground for the lightning transient protective devices in this product to be effective.
  • Page 64: Auxiliary Device Current Draw Worksheet

    Do not connect the battery until all devices have been wired to the control. 2. Attach the Red and Black wires on the battery connector cable as follows: a) Red to the positive (+) battery tab on the control board.* b) Black to the negative (–) battery tab on the control board.* This not required if wires are already connected to the battery tabs on the control.
  • Page 65: Alpha Descriptor Programming

    Vocabulary list (on a following page) shown in boldface type. The Phone module will not provide annunciation of the other words. If a 4285 Phone module is added to an existing VIA-30PSE system, the Alpha descriptors presently in the system should be re-programmed, selecting from those words shown in boldface type in the Alpha Vocabulary list.
  • Page 66 4. Press “0” (No).* The system will then automatically display the default descriptor for zone 1. The procedure for adding custom words to the built-in vocabulary will be found later under “Adding Custom Words”. ↓ If a descriptor was not entered previously Default Descriptor for zone 1, the default descriptor for zone ZN 0 1...
  • Page 67: Alternate Method For Programming Zone Descriptors

    9. Press “6” to accept the selected ZN 0 1 BA CK word. DO O R Note: If these are the only words you are using for the descriptor, ↑ press “8” instead of “6” to save them Flashing Cursor if “6” is in memory.
  • Page 68: Adding Custom Words

    4. For selection of the next word (e.g., DOOR), repeat step 3, as follows: Press key [3] until the first letter of the next word appears (e.g., "D"). Then press [6] to display the first available word beginning with that letter (e.g. DAUGHTERS).
  • Page 69: Alpha Vocabulary List (For Entering Zone Descriptors)

    ALPHA VOCABULARY LIST (For Entering Zone Descriptors) NOTE : Some rarely-used words appearing in previously published lists have been deleted from the list below. Use only this list for selecting zone descriptors. (Word Space) • 057 DOOR • 106 LAUNDRY •...
  • Page 70 WWW.DIYALARMFORUM.COM 13 –6...
  • Page 71: Sequential Mode

    Section 14. SEQUENTIAL MODE (for 5800 Series Wireless Transmitters) (Use this mode only after all other zone information has been programmed, including transmitter loop numbers). There are two methods of enrolling – you can enroll each transmitter into the system as you are entering the zone information in field 56 (the procedure will be found in the WIRELESS (RF) ZONE EXPANSION section), or you can enroll all the transmitters in 83 menu mode after all other zone...
  • Page 72 5. This prompt is displayed when the system has found the next zone 10 Input S/N: which needs to be enrolled. Axxx xxxx The system will respond to the first serial number transmitted. A serial number may be enrolled by one of two methods: a) Enter the 7 digit serial number printed on the transmitter b) Activate the transmitter by faulting or restoring the input you wish to use for that zone (e.g., press a button, open or close a door, etc.).
  • Page 73 7. The system will search for the next zone that does not have a serial number associated with it. If one is found, the prompt in step 5, along with the appropriate zone number, will be displayed. Follow steps 5 and 6 for the remaining wireless zones.
  • Page 74 WWW.DIYALARMFORUM.COM 14 –4...
  • Page 75: System Communication

    This is the “expanded” digit. 4+2 Format Comprises a 4-digit subscriber number and 2-digit report code. Ademco Contact ID Comprises a 4-digit subscriber number, 1-digit event qualifier Reporting Format ("new" or "restore"), 3-digit event code, and 3-digit zone number, user number, or system status number (see the following page).
  • Page 76 [1] + [ ], or [A] = 95 Duress = 8 [3] + [#], or [C] = 96 Tamper = 9 Ademco Contact ID Reporting takes the following format: CCCC Q EEE GG ZZZ where: CCCC = Customer (subscriber) ID Q = Event qualifier, where:...
  • Page 77: Table Of Contact Id Event Codes

    TABLE OF CONTACT ID EVENT CODES Code Definition Code Definition Fire Alarm Exit Error Alarm Duress Trouble (Global) Alarm, 24-hour Silent RF Sensor Tamper Alarm, 24-hour Audible Panic RF Sensor Low Battery Alarm, Perimeter, Burg. O/C by User Alarm, Interior, Burg. Cancel by User Alarm, Entry/Exit, Burg.
  • Page 78 REPORT FORMAT, PRIMARY/SECONDARY Determines which format is to be used to report to the central station. 0 = 3+1; 4+1 ADEMCO Lo Speed Standard (this is the default) 1 = 3+1; 4+1 Radionics Standard 2 = 4+2 ADEMCO Lo Speed Standard...
  • Page 79 A "0" ( not "# + 10") in both boxes will disable the report. With Ademco Contact ID Reporting: Enter any digit (other than "0") in the first box, to enable zone to report This is an "enabling" code only and is disregarded in the actual reporting to the central office.
  • Page 80 Press 62 AC LOSS REPORT CODE Reports with Subscriber No. Timing of this report is random with up to a 48-minute delay. The Restore report has a random delay of up to about 12 minutes. If AC restores before the report goes out, there is no AC restore report.
  • Page 81 Press 73 AC RESTORE REPORT CODE This is sent when AC power has been restored after an AC power outage. Press 74 LOW BAT RESTORE REPORT CODE This is sent when a system low battery condition is restored to normal. Press 75 RF XMTR.
  • Page 82 WWW.DIYALARMFORUM.COM...
  • Page 83: Testing The System

    Section 16. TESTING THE SYSTEM Test Procedure After installation is completed, the System should be carefully tested, as follows: 1. With the System in the disarmed state, check that all zones are intact. If a NOT READY message is displayed, press the [ ] key to display the faulted zone(s).
  • Page 84: To The Installer

    To test the wireless part of the system and the RF Receiver, perform the two following tests: Transmitter Sniffer Mode and Go/NoGo Test Mode . TRANSMITTER SNIFFER MODE Make sure the system is disarmed before trying to enter this mode. Key Installer code + # + 3.
  • Page 85: System Operation

    Section 17. SYSTEM OPERATION Security Codes Installer Code The installer programs the 4-digit Installer Code initially as part of the programming procedure. The factory default Installer code is "4-1-1-1", but may be changed in field 20. Note: The Installer Code is defined as User #1. The Installer code is the only code that can allow re-entry into programming mode.
  • Page 86: Keypad Functions

    Keypad Functions General Note that if you enabled QUICK ARM (field 21), the [#] key can be pressed Information instead of entering the security code, for any of the arming procedures (Away, Stay, Instant, Maximum, etc.). The security code is always required, however, when disarming the system.
  • Page 87: Panic Keys

    Panic Keys There are three individual panic keys or, on some keypads, panic key pairs. If programmed, they can be used to manually initiate alarms and send a report to the central station. Each key (or key pair) can be individually programmed for 24-hour Silent, Audible, Personal or Fire Emergency responses.
  • Page 88: Trouble Conditions

    • The " " display, etc. will also result if an alarm from an exit or EXIT ALARM interior zone occurs within two minutes after the end of an exit delay. In any of the previous cases, use a second OFF sequence (code plus OFF key) to clear the display.
  • Page 89: Troubleshooting Guide

    Section 18. TROUBLESHOOTING GUIDE SYSTEM (including Wireless) SYMPTOM POSSIBLE CAUSE REMEDY 1. Transmitter signal not 1a. Transmitter or 4281/5881 not properly pow- Check or change transmitter's bat tery. received at 4281/5881. ered. Check the control's AC power. 1b. If Transmitter is 5827/5827BD , house ID 1b.
  • Page 90 2b. Telephone connection not secure. 2b. Check all connections. 2c. Digital communicator malfunctioning 2c. Check with a different VIA-30PSE. 2d. Telephone number in program needs prefix 2d. Program prefix or access code into the or access code.
  • Page 91: Contacting Technical Support

    (1200 – 9600 Baud, 8 Data Bits, 1 Start/Stop Bit, No Parity) ATLIS FAX – Automated Fax Retrieval System: 1–800–573–0153 1–516–921–6704/Ext. 1667 ADEMCO World Wide Web Page: HTTP//: WWW. ADEMCO. COM INTERNET E-Mail Address: Ademco_Tech_SPRT @ Ademco–165 . Ademco . com WWW.DIYALARMFORUM.COM 18 –3...
  • Page 92 WWW.DIYALARMFORUM.COM 18 –4...
  • Page 93: Specifications & Accessories

    1. Physical: 12-1/2" W x 14-1/2" H x 3" D (318mm x 368mm x 76mm). SECURITY CONTROL 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321/TF2 (in U.S.A.). RECHARGEABLE BACK-UP BATTERY: 12VDC, 4AH (Gel type). Charging Voltage: 13.8VDC.
  • Page 94 200ft (60m) nominal indoors from wireless transmitters (the (5800 System) actual range to be determined with system in TEST mode). 5. Zones: (With the Ademco VIA-30PSE ) 4281L: accepts up to 4 transmitters. 4281M or 4281H: accepts up to 8 transmitters. 5881L: accepts up to 8 transmitters.
  • Page 95: Accessories (Compatible Devices)

    No. 1321 16.5VAC, 25VA Plug-In Transformer (in U.S.A.) No. 1321CN 16.5VAC, 25VA Plug-In Transformer (in Canada) Sounders Ademco AB-12M 10” Motor bell & box. UL Grade A. 100mA current Motorized Bell & Box draw. Ademco 1011BE12M 10” Motor bell & box. UL Listed. 100mA current Motorized Bell &...
  • Page 96 Compatible 4-Wire System Sensor Models Smoke/Combustion Detectors 1412 4-wire ionization products of combustion detector. 2412 4-wire photoelectric smoke detector. 2412TH 4-wire photoelectric smoke detector w/135º F (57º C) heat detector. A77–716B EOL relay module (supervisory module for wired 4-wire fire zone).
  • Page 97: Appendix A: Regulatory Agency Statements

    APPENDIX A: REGULATORY AGENCY STATEMENTS FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information: This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception.
  • Page 98 425mA 14AH ‡ Note: Use two batteries, connected in parallel. Obtain an Ademco No. 4100EOLR Resistor Kit. A dual battery harness is provided with the kit. The kit also contains EOL resistors with spade lug/heat shrink tubing construction which has been approved by UL and CSFM for fire zone usage. Both batteries will fit inside the panel's cabinet.
  • Page 99 CANADIAN DEPARTMENT OF COMMUNICATIONS (DOC) STATEMENT NOTICE The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company.
  • Page 100 WWW.DIYALARMFORUM.COM A –4...
  • Page 101: Appendix B: Limitations Of This Alarm System

    APPENDIX B: WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of rea sons.
  • Page 102: Limited Warranty

    24 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply.
  • Page 103: Summary Of Connections Diagram

    (8 ADD'L EOLR WIRED ZONES PLUS 2 OUTPUT RELAYS) POWER SUPER- – -OR- BLACK BATTERY VIOLET VISION CHARGING ADEMCO No. 4204 RELAY MODULE 12V, 4AH RELAY 4-WIRE SMOKE VOLTAGE (4 OUTPUT RELAYS) (e.g. ADEMCO MODULE OR COMBUSTION 13.8VDC No. 467) •...
  • Page 104 ALARM D E VIC E MANUFAC TURING C O . A DIVISION OF PITTWAY CORPORATION 165 Eileen Way, Syosset, New York 11791 Copyright © 1997 PITTWAY CORPORATION WWW.DIYALARMFORUM.COM N7225V2 4/97...

Table of Contents