Parameter
Function name
No.
PID Deviation
A077
Reverse Output
PID Variable Range
A078
Limit
PID Feedforward
A079
Selection
A081
1st AVR Selection
A281
2nd AVR Selection
1st Motor Rated Volt-
A082
age Selection
2nd Motor Rated
A282
Voltage Selection
A083
AVR Filter Time Constant 0.000 to 10.000
AVR Gain at Deceler-
A084
ation
Operation Mode
A085
Selection
Energy-saving
A086
Response/Accuracy
Adjustment
1st Acceleration
A092
Time 2
2nd Acceleration
A292
Time 2
1st Deceleration
A093
Time 2
2nd Deceleration
A293
Time 2
1st
A094
2-step Acceleration/
Deceleration Selection
2nd
A294
2-step Acceleration/
Deceleration Selection
1st
A095
2-step Acceleration
Frequency
2nd
A295
2-step Acceleration
Frequency
1st
A096
2-step Deceleration
Frequency
2nd
A296
2-step Deceleration
Frequency
Acceleration
A097
Pattern Selection
Deceleration
A098
Pattern Selection
*1. The digit shift display mode can be used.
*2. In high-frequency mode.
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Monitor or data range
00: Disabled (Deviation = Target value
− Feedback value)
01: Enabled (Deviation = Feedback
value − Target value)
0.0 to 100.0
00: Disabled
01: O (Voltage)
02: OI (Current)
00: Always ON
01: Always OFF
02: OFF during deceleration
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
50. to 200.
00: Normal operation
01: Energy-saving operation
0.0 to 100.0
*1
0.00 to 3600.00
00: Switch via 2CH terminal (multi-func-
tion input: 09)
01: Switch by setting (A095/A295/
A096/A296)
02: Switch only during forward/reverse
switching
0.00 to 590.00
00: Line
01: S-shape curve
02: U-shape curve
03: Inverted U-shape curve
04: EL-S-shape curve
4 Parameter List
Changes
Default
Set
during
data
data
RUN
00
Enabled
0.0
Enabled
00
Enabled
02
Enabled
02
Enabled
200/400
Disabled
200/400
Disabled
0.300
Enabled
100.
Enabled
00
Disabled
50.0
Enabled
10.00
Enabled
*2
(15.00)
10.00
Enabled
*2
(15.00)
10.00
Enabled
*2
(15.00)
10.00
Enabled
*2
(15.00)
00
Disabled
00
Disabled
0.00
Enabled
0.00
Enabled
0.00
Enabled
0.00
Enabled
01
Disabled
01
Disabled
Unit
Page
−
P. 7-44
%
−
−
P. 7-42
−
V
P. 5-20
V
s
4
P. 7-42
%
−
P. 7-50
%
s
−
P. 5-36
Hz
−
P. 5-33
4 - 11