Using an Analog Voltage Input or Analog Current Input by Switching
To switch between the analog voltage and analog current inputs to set the frequency reference, set the
parameters as shown in the table below.
This enables switching between the frequency reference input (voltage reference) and frequency refer-
ence input (current reference) terminals.
To switch between these analog input signals, use the terminal AT (Analog input switching) allocated to
a multi-function input terminal.
When the terminal AT is input, the frequency reference input (current reference) terminal is enabled.
V
• Frequency reference input (Voltage reference), between O and L: 0 to 10 VDC
• Frequency reference input (Current reference), between OI and L: 4 to 20 mA
Note By default, each analog input signal is set to reach the maximum frequency at 9.8 V or 19.8 mA.
Parameter No.
A001/A201
A005
C001 to C007
Using an Analog Voltage Input and Volume Control by Switching
To switch between an analog voltage input and the volume control on the Digital Operator (Model:
3G3AX-OP01) to set the frequency reference, set the parameters as shown in the table below.
This enables switching between the frequency reference input (voltage reference) and the volume con-
trol on the 3G3AX-OP01.
To switch the reference input, use the terminal AT (Analog input switching) allocated to a multi-function
input terminal.
When the terminal AT is input, the volume control on Digital Operator (Model: 3G3AX-OP01) is
enabled.
V
• Frequency reference input (Voltage reference), between O and L
• Volume control on Digital Operator (Model: 3G3AX-OP01)
Note By default, each analog input signal is set to reach the maximum frequency at 9.8 V or 19.8 mA.
Parameter No.
A001/A201
A005
C001 to C007
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
A
Function name
1st/2nd Frequency
01:
Reference Selection
00:
O/FI Selection
Multi-function Input
16:
1 to 7 Selection
Function name
1st/2nd Frequency
01:
Reference Selection
02:
O/OI Selection
Multi-function Input
16:
1 to 7 Selection
Data
Control circuit terminal block
(Analog input)
Switch between O (Voltage)
and FI (Current)
AT (Analog input switching)
0 to 10 VDC
:
Data
Control circuit terminal block
(Analog input)
Switch between O (Voltage)
and volume via terminal AT
(Enabled only when
3G3AX-OP01 is used.)
AT (Analog input switching)
5 Basic Settings
Default data
Unit
02
00
Default data
Unit
02
00
5 - 27
5