Group A: Standard Function Parameters - Omron MX2 Series User Manual

Multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

4-3-1

Group A: Standard Function Parameters

Parameter
Function name
No.
1st Frequency Refer-
A001
ence Selection
2nd Frequency Refer-
A201
ence Selection
1st RUN Command
A002
Selection
2nd RUN Command
A202
Selection
A003
1st Base Frequency
A203
2nd Base Frequency
1st Maximum Fre-
A004
quency
2nd Maximum Fre-
A204
quency
A005
O/OI Selection
A011
O Start Frequency
A012
O End Frequency
A013
O Start Ratio
A014
O End Ratio
A015
O Start Selection
A016
Analog Input Filter
DriveProgramming
A017
Function Selection
*1. This setting is enabled when the Digital Operator with the volume control (Model: 3G3AX-OP01) is connected.
*2. In high-frequency mode.
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Monitor or data range
00: Digital Operator (Volume)
01: Control circuit terminal block (Ana-
log input)
02: Digital Operator (F001)
03: Modbus communication
04: Option
06: Pulse train frequency
07: DriveProgramming
10: Operation function output
01: Control terminal block (DrivePro-
gramming)
02: Digital Operator
03: Modbus communication
04: Option
30.0 to 1st Maximum Frequency (A004)
30.0. to 2nd Maximum Frequency (A204)
1st Base Frequency (A003) to 590.0
2nd Base Frequency (A203) to 590.0
00: Switch between O (Voltage) and OI
(Current)
02: Switch between O (Voltage) and vol-
*1
ume
03: Switch between OI (Current) and
*1
volume
0.00 to 590.00
0.00 to 590.00
0. to O End Ratio
O Start Ratio to 100.
00: O Start Frequency (A011)
01: 0 Hz
1. to 30.
31. (500-ms filter with ±0.1-Hz hystere-
sis)
00: Disabled
01: Enabled (Start/stop via multi-func-
tion input PRG terminal)
02: Enabled (Start/stop via power on/
off)
Default
Set
data
data
*1
02
02
02
02
60.0
*2
(580.0)
60.0
*2
(580.0)
60.0
*2
(580.0)
60.0
*2
(580.0)
00
0.00
0.00
0.
100.
01
8.
00
4 Parameter List
Changes
during
Unit
Page
RUN
Disabled
P. 5-23
Disabled
Disabled
P. 5-21
Disabled
Disabled
Hz
P. 5-20
Disabled
Hz
Disabled
Hz
P. 5-20
Disabled
Hz
Disabled
P. 7-22
Enabled
Hz
Enabled
Hz
Enabled
%
P. 7-25
Enabled
%
Enabled
Enabled
P. 7-24
Enabled
P. 7-105
4 - 7
4

Advertisement

Table of Contents
loading