Base Frequency And Maximum Frequency Of Motor - Omron MX2 Series User Manual

Multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

5 Basic Settings
5-3-3

Base Frequency and Maximum Frequency of Motor

To configure the V/f control characteristics output to the motor, set the base frequency and maximum
frequency of your motor.
For the base frequency, set the rated frequency of the motor (the frequency listed on the motor rating
nameplate).
For the maximum frequency, set the highest frequency required for your application. However, do not
exceed the maximum rotation speed of the motor.
Then, set the 1st/2nd Motor Rated Voltage Selection (A082/A282) to the rated voltage of the motor.
Parameter
No.
1st Base Frequency
A003
A203
2nd Base Frequency
1st Maximum Frequency
A004
A204
2nd Maximum Frequency
1st/2nd Motor Rated
A082/A282
Voltage Selection
*1. To enable the switching to the 2nd control, set one of the Multi-function Input 1 to 7 Selection (C001 to C007) to
08 (SET) and turn ON that terminal.
*2. In high-frequency mode.
Output
voltage
1st/2nd Motor Rated
Voltage Selection
(A082/A282)
Precautions for Correct Use
• Motors whose rated frequency exceed 60 Hz are regarded as special motors.
For these motors, check the rated motor current and select an appropriate inverter based on
the rated current of the inverter.
If you must use the motor at higher than 400 Hz, use the high-frequency mode.
• Do not set the base frequency to lower than the motor rated frequency. Doing so may cause
overload or motor burnout.
• Do not set the motor rated voltage to the motor rated frequency or higher. Doing so may
cause an overload or motor burnout.
5 - 20
Function name
30.0 to 1st Maximum Frequency (A004)
30.0 to 2nd Maximum Frequency (A204)
*1
1st Base Frequency (A003) to 590.0
*1
2nd Base Frequency (A203) to 590.0
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
1st/2nd Base
Frequency
(A003/A203)
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Data
Output frequency
1st/2nd Maximum
Frequency
(A004/A204)
Default data
Unit
*2
Hz
60.0 (580.0)
*2
Hz
60.0 (580.0)
*2
Hz
60.0 (580.0)
*2
Hz
60.0 (580.0)
200/400
V

Advertisement

Table of Contents
loading

Table of Contents