Analog I/O Settings; Analog Input (O, Oi) - Omron MX2 Series User Manual

Multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

7 Other Functions
7-3

Analog I/O Settings

This section describes the analog I/O signal settings for this inverter.
7-3-1

Analog Input (O, OI)

This inverter has two types of external analog input terminals.
Frequency reference (Analog voltage input) between terminals O and L
This terminal also treats input via the variable resistor (volume) as voltage input to the
inverter.
Frequency reference (Analog current input) between terminals OI and L
For 0 to 20 mA, set A103 to 0%.
For analog input start/end settings, refer to 7-3-5 Analog Input Start/End Function Settings on page 7-25.
Note 1. By default, each analog input signal is adjusted to reach the maximum frequency at 9.8 V or 19.8 mA.
2. If an excessive current is applied to the terminal OI, an E26 (analog current input error) will occur.
The table below shows analog-input related functions. Set each function according to your application.
Parameter
No.
Frequency
A001/A201
reference
A071
PID feedback
selection
A076
A071
PID feedforward
selection
A079
A001/A201
A141
A142
Calculation
frequency
A143
b040
Torque limit
7 - 22
Setting item
Function name
1st/2nd Frequency
*1
Reference Selection
PID Selection
*2
PID Feedback
Selection
PID Selection
*3
PID Feedforward
Selection
1st/2nd Frequency
Reference Selection
Calculation Frequency
Selection 1
Calculation Frequency
Selection 2
Calculation Function
Operator Selection
*4
Torque Limit Selection
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
: 0 to 10 V
: 4 to 20 mA
Data
01:
Control circuit terminal
block
(Analog input)
01:
Enabled
02:
Enabled (Reverse out-
put enabled)
00:
OI (Current)
01:
O (Voltage)
01:
Enabled
02:
Enabled (Reverse out-
put enabled)
01:
O (Voltage)
02:
OI (Current)
10:
Operation function
output
02:
Input O (Voltage)
03:
Input OI (Current)
Addition (A141 + A142)
00:
Subtraction (A141 −
01:
A142)
Multiplication (A141 
02:
A142)
02:
Analog voltage input
Default
Unit
data
02
00
00
00
00
02
02
03
00
00

Advertisement

Table of Contents
loading

Table of Contents