6.10

Selection example of wires

To comply with the IEC/EN/UL/CSA standard for wiring, use the wires described in the MR-J5 Safety
Instructions and Precautions for AC Servos (IB(NA)-0300391). To comply with other standards, use wires that
comply with each standard.
Selection conditions for the wire size are as follows.
Construction requirements: Single wire set in midair
Wiring length: 30 m or less
The following shows the wires used for wiring. Use the wires given in this section or equivalent wires.
For the MR-CM simple converter wiring, refer to the following.
Page 294 I/O wires
For the FR-XC-(H) multifunction regeneration converter wiring, refer to the following.
Page 300 Wiring and peripheral options
Power supply
(2) Control circuit
power supply lead
6 OPTIONS AND PERIPHERAL EQUIPMENT
326
6.10 Selection example of wires
(1) Main circuit power supply lead
Regenerative option
(3) Regenerative option lead
Servo amplifier
L1
U
L2
V
L3
W
L11
(4) Servo motor power lead
L21
C
P+
M