13.7
Absolute position detection system
Structure
An absolute position linear encoder is required to configure an absolute position detection system under fully closed loop
control using a linear encoder.
In this case, an encoder battery need not be installed to the servo amplifier.
When a battery backup type rotary encoder is used, an absolute position detection system can be configured by installing the
encoder battery to the servo amplifier.
When a batteryless rotary encoder is used, the encoder battery need not be mounted to the servo amplifier.
• Use an absolute position type encoder for the load-side encoder.
Using an incremental type encoder triggers [AL. 037 Parameter error].
• When using the Mitsubishi Electric direct drive motor for the load-side encoder, the Z-phase must be passed
through before homing.
• Switching between semi closed loop control and fully closed loop control cannot be performed. Set [Pr.
PE01.0 Fully closed loop function selection] to "0" (Always enabled). If [Pr. PE01.0] is set to "1" (switching
by "fully closed loop selection" from the controller (C_CLD) and by the input device "fully closed loop
selection" (CLD)), [AL. 037] occurs.
• Use the encoder within the range of 32-bit absolute position data. When the degree unit is used, the infinite
feed function is enabled. For details, refer to "Infinite feed function" in the following manual.
MR-J5 User's Manual (Function)
• When a linear encoder is used for the load-side encoder, absolute position-related alarms ([AL. 025
Absolute position erased]) and warnings ([AL. 092 Battery cable disconnection warning] and [AL. 09F
Battery warning]) are not detected.
Precautions
When the absolute position detection system is configured with a rotary encoder, the battery life will be shortened because the
current consumption is increased as the power from the battery is supplied to both the servo motor-side and the load-side
encoder.
To set [Pr. PL01.0 Servo motor magnetic pole detection selection] to "0" (Magnetic pole detection disabled) by using the direct
drive motor manufactured by Mitsubishi Electric, connect batteries and the absolute position storage unit (MR-BTAS01).
Otherwise, [AL. 092 Battery cable disconnection warning] or [AL. 09F Battery warning] is detected. When [AL. 092] or [AL.
09F] occurs, setting [Pr. PL01.0] to "0" may not disable the magnetic pole detection.
When the fully closed loop system is used with a Mitsubishi Electric-manufactured direct drive motor connected to the servo
motor side and an absolute position type linear encoder connected to the load side and [Pr. PL01.0] is set to "0", set [Pr.
PA03.0 Absolute position detection system selection] to "1" (enabled (absolute position detection system)), and reset the
controller or cycle the power to reflect the parameter setting. After reflecting the setting, cycle the power and turn on the Z-
phase.
13 USING A FULLY CLOSED LOOP SYSTEM
616
13.7 Absolute position detection system