Selection Example Of Wires - Mitsubishi Electric Melservo HF-KN Series Instruction Manual

General-purpose ac servo
Table of Contents

Advertisement

4. CONNECTION OF SERVO AMPLIFIER AND SERVO MOTOR

4.3 Selection example of wires

The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
When using the 600 V Grade heat-resistant polyvinyl chloride insulated wire (HIV wire)
Wire size selection examples for HIV wires are indicated below.
POINT
Wires indicated in this section are separated wires. When using a cable for
power line (U, V, and W) between the servo amplifier and servo motor, use a
600 V grade EP rubber insulated chloroprene sheath cab-tire cable (2PNCT).
For selection of cables, refer to appendix 6.
To comply with the UL/CSA standard, use the wires shown in appendix 4 for
wiring. To comply with other standards, use a wire that is complied with each
standard.
Selection condition of wire size is as follows.
Construction condition: One wire is constructed in the air.
Wire length: 30 m or less
Servo amplifier
U
V
W
Table 4.1 Wire size selection example 2 (HIV wire)
Servo motor
HF-KN13
HF-KN23
HF-KN43
HF-KN73
HF-SN52
HF-SN102
HF-SN152
HF-SN202
HF-SN302
Note. It is for 10 m wire length. When fabricating an extension cable, use 1.25 mm
1) Servo motor power lead
2) Electromagnetic
brake lead
Encoder cable
1) U/V/W/
0.75 (AWG 18) (Note)
1.25 (AWG 16)
2 (AWG 14)
3.5 (AWG 12)
4 - 7
Servo motor
U
V
Motor
W
B1
Electromagnetic
brake
B2
Encoder
2
Wires [mm
]
2) B1/B2
0.5 (AWG 20) (Note)
1.25 (AWG 16)
2
(AWG 16).