9 | Safety function STO
9.6.2 Direct switch-off with emergency stop switch and monitoring of the wiring
+24V
Fig. 10: Direct switch-off with emergency stop switch and monitoring of the wiring
44
Safety
X2B
1 - STO1-
2 - STO1+
3 - STO2-
4 - STO2+
5 - OUT 3
6 - OUT 4
7 - 0V
8 - P24V-IN
The shown circuit detects wiring faults in the area of the emergency stop
switchgear and the supply line. A possible short circuit on the primary side of the
emergency stop switchgear (ground and DC +24 V) and a short circuit on the sec-
ondary side of the device or within the wiring leads either directly or with closed
contacts to a short circuit of the supply, whereby an upstream 24 V fuse trips.
In addition to the two applications shown here with an emergency stop switching
device, other sensors (such as door switches, etc.) can be used in the same way.