Esd (Electrostatic Discharge) Connection; Installation Procedure; Figure 1: Distance Between The Vertical Supports - Mellanox Technologies MSX6518-6R Hardware Installation Manual

324 port infiniband fdr switch platform
Table of Contents

Advertisement

324 Port InfiniBand FDR Switch Platform Hardware Installation Guide
The vertical supports may have to be moved so that the vertical support closest to the door
is 6 cm from the inside of the door. This may be required so that the shelf does not pro-
trude from the rack.

1.6.2 ESD (ElectroStatic Discharge) Connection

Before starting any procedure on the SX6518 switch system do the following.
Step 1.
Step 2.

1.6.3 Installation Procedure

Mellanox Technologies

Figure 1: Distance Between the Vertical Supports

If you move the vertical supports make sure that you reinstall them vertically
plumb.
Put an ESD prevention wrist strap on your wrist, and make sure there is good
contact between your body and the strap.
Plug the other end of the wrist strap to a valid ground. Make sure that this is a
tight fit.
Installing the chassis will be a lot easier if you can remove the sides of the rack.
Vertical Supports
This edge of the shelf
must be as close as
possible to the inside of
the door when closed.
Rev 1.0
13