Analog Output; Control Card, Rs485 Serial Communication; Digital Outputs - Danfoss VLT AQUA Drive FC 202 Operating Manual

355-800 kw, enclosure sizes e1h-e4h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Operating Guide | VLT® AQUA Drive FC 202
Maximum voltage on input
Input resistance, R
i
Pulse input accuracy (0.1–1 kHz)
Encoder input accuracy (1–11 kHz)
1
FC 302 only.
2
Encoder inputs: 32=A and 33=B.

9.6.5 Analog Output

Number of programmable outputs
Terminal number
Current range at analog output
Maximum load GND - analog output less than
Accuracy on analog output
Resolution of analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

9.6.6 Control Card, RS485 Serial Communication

Terminal number
Terminal number 61
The RS485 serial communication circuit is galvanically isolated from the supply voltage (PELV).

9.6.7 Digital Outputs

Programmable digital/pulse outputs
Terminal number
(1)
Voltage level at digital/frequency output
Maximum output current (sink or source)
Maximum load at frequency output
Maximum capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
1
Terminals 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Danfoss A/S © 2020.01
Specifications
Approximately 4 kΩ
Maximum error: 0.1% of full scale
Maximum error: 0.05% of full scale
0/4 to 20 mA
Maximum error: 0.8% of full scale
68 (P, TX+, RX+), 69 (N, TX-, RX-)
Common for terminals 68 and 69
Maximum error: 0.1% of full scale
AQ275652274277en-000101 / 130R0708| 139
28 V DC
1
42
500 Ω
8 bit
2
27, 29
0–24 V
40 mA
1 kΩ
10 nF
0 Hz
32 kHz
12 bit