Operating Guide | VLT® AQUA Drive FC 202
8.4.42 ALARM 46, Power Card Supply
Cause
The supply on the power card is out of range. Another reason can be a defective heat sink fan.
There are 3 supplies generated by the switch mode supply (SMPS) on the power card:
24 V.
5 V.
±18 V.
®
When powered with VLT
24 V DC Supply MCB 107, only 24 V and 5 V supplies are monitored. When powered with 3-phase mains
voltage, all 3 supplies are monitored.
Troubleshooting
Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
If a 24 V DC supply is used, verify proper supply power.
Check for a defective heat sink fan.
8.4.43 WARNING 47, 24 V Supply Low
Cause
The supply on the power card is out of range.
There are 3 supplies generated by the switch mode supply (SMPS) on the power card:
24 V
5 V
±18 V
Troubleshooting
Check for a defective power card.
8.4.44 WARNING 48, 1.8 V Supply Low
Cause
The 1.8 V DC supply used on the control card is outside of the allowed limits. The supply is measured on the control card.
Troubleshooting
Check for a defective control card.
If an option card is present, check for overvoltage.
116 | Danfoss A/S © 2020.01
Maintenance, Diagnostics, and
Troubleshooting
AQ275652274277en-000101 / 130R0708