Wiring Configuration For Automatic Motor Adaptation Without T27; Wiring Configuration: Speed - Danfoss VLT AQUA Drive FC 202 Operating Manual

355-800 kw, enclosure sizes e1h-e4h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Operating Guide | VLT® AQUA Drive FC 202

7.1.2 Wiring Configuration for Automatic Motor Adaptation without T27

Table 17: AMA without T27 Connected
Drive
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39

7.1.3 Wiring Configuration: Speed

Table 18: Analog Speed Reference (Voltage)
Drive
50
+10 V
+
A IN
53
A IN
54
COM
55
-
A OUT
42
0–10 V
COM
39
U - I
A53
Danfoss A/S © 2020.01
Parameters
Function
Parameter 1-29 Automatic Motor Adaptation (AMA)
Parameter 5-12 Terminal 27 Digital Input
*=Default value
Notes/comments: Parameter group 1-2* Motor Data must be set ac-
cording to motor.
Parameters
Function
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-11 Terminal 53 High Voltage
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
*=Default value
Notes/comments:
D IN 37 is an option.
Wiring Configuration Examples
Setting
[1] Enable complete
AMA
[0] No operation
Setting
0.07 V*
10 V*
0 Hz
50 Hz
AQ275652274277en-000101 / 130R0708| 75

Advertisement

Table of Contents
loading

Table of Contents