Danfoss VLT AQUA Drive FC 202 Operating Manual page 109

355-800 kw, enclosure sizes e1h-e4h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Operating Guide | VLT® AQUA Drive FC 202
Troubleshooting
Check for motor overheating.
Check if the motor is mechanically overloaded.
Check that the motor current set in parameter 1-24 Motor Current is correct.
Ensure that the motor data in parameters 1-20 to 1-25 is set correctly.
If an external fan is in use, check that it is selected in parameter 1-91 Motor External Fan.
Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the drive to the motor more accurately and reduces
thermal loading.
8.4.11 WARNING/ALARM 11, Motor Thermistor Overtemp
The motor thermistor indicates that the motor temperature is too high.
Troubleshooting
Check for motor overheating.
Check that the thermistor is securely connected.
Check if the motor is mechanically overloaded.
When using terminal 53 or 54, check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage
input) and terminal 50 (+10 V supply). Also check that the terminal switch for 53 and 54 is set for voltage. Check that parameter 1-93
Thermistor Resource selects 53 or 54.
When using terminal 18, 19, 31, 32, or 33 (digital inputs), check that the thermistor is connected correctly between the digital input
terminal used (digital input PNP only) and terminal 50. Select the terminal to use in parameter 1-93 Thermistor Resource.
8.4.12 WARNING/ALARM 12, Torque Limit
Cause
The torque has exceeded the value in parameter 4-16 Torque Limit Motor Mode or the value in parameter 4-17 Torque Limit Generator
Mode. Parameter 14-25 Trip Delay at Torque Limit can change this warning from a warning-only condition to a warning followed by an
alarm.
Troubleshooting
If the motor torque limit is exceeded during ramp-up, extend the ramp-up time.
If the generator torque limit is exceeded during ramp-down time, extend the ramp-down time.
If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque.
Check the application for excessive current draw on the motor.
8.4.13 ALARM 14, Earth (Ground) Fault
Cause
There is current from the output phase to ground, either in the cable between the drive and the motor, or in the motor itself. The
current transducers detect the ground fault by measuring current going out from the drive and current going into the drive from the
motor. Ground fault is issued if the deviation of the 2 currents is too large. The current going out of the drive must be the same as the
current going into the drive.
Danfoss A/S © 2020.01
Maintenance, Diagnostics, and
Troubleshooting
AQ275652274277en-000101 / 130R0708| 107

Advertisement

Table of Contents
loading

Table of Contents