Danfoss VLT AQUA Drive FC 202 Operating Manual page 128

355-800 kw, enclosure sizes e1h-e4h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Operating Guide | VLT® AQUA Drive FC 202
Troubleshooting
Check wiring.
Check the on-board temperature sensor.
Replace fan power card.
8.4.96 ALARM 423, FPC Updating
Cause
The alarm is generated when the fan power card reports it has an invalid PUD. The control card attempts to update the PUD. A
subsequent alarm can result depending on the update. See Alarm 424, FPC Update Successful and Alarm 425 FPC Update Failure.
8.4.97 ALARM 424, FPC Update Successful
Cause
This alarm is generated when the control card has successfully updated the fan power card PUD.
Troubleshooting
Press [Reset] to stop the alarm.
8.4.98 ALARM 425, FPC Update Failure
Cause
This alarm is generated after the control card failed to update the fan power card PUD.
Troubleshooting
Check the fan power card wiring.
Replace fan power card.
Contact supplier.
8.4.99 ALARM 426, FPC Config
Cause
The number of found fan power cards does not match the number of configured fan power cards. See parameter group 15-6* Option
Ident for the number of configured fan power cards.
Troubleshooting
Check fan power card wiring.
Replace fan power card.
126 | Danfoss A/S © 2020.01
Maintenance, Diagnostics, and
Troubleshooting
AQ275652274277en-000101 / 130R0708