Danfoss VLT AQUA Drive FC 202 Operating Manual page 117

355-800 kw, enclosure sizes e1h-e4h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Operating Guide | VLT® AQUA Drive FC 202
8.4.38 WARNING 41, Overload of Digital Output Terminal 29
Troubleshooting
Check the load connected to terminal 29 or remove the short-circuit connection.
Check parameter 5-00 Digital I/O Mode and parameter 5-02 Terminal 29 Mode.
8.4.39 WARNING 42, Ovrld X30/6-7
Troubleshooting
For terminal X30/6:
Check the load connected to the terminal, or remove the short-circuit connection.
Check parameter 5-32 Term X30/6 Digi out (MCB 101) (VLT® General Purpose I/O MCB 101).
For terminal X30/7:
Check the load connected to the terminal, or remove the short-circuit connection.
Check parameter 5-33 Term X30/7 Digi Out (MCB 101) (VLT® General Purpose I/O MCB 101).
8.4.40 ALARM 43, Ext. Supply
Either connect a 24 V DC external supply or specify that no external supply is used via parameter 14-80 Option Supplied by External
24VDC, [0] No. A change in parameter 14-80 Option Supplied by External 24VDC requires a power cycle.
Cause
VLT® Extended Relay Option MCB 113 is mounted without 24 V DC.
Troubleshooting
Choose 1 of the following:
Connect a 24 V DC external supply.
Specify that no external supply is used via parameter 14-80 Option Supplied by External 24VDC, [0] No. A change in parameter 14-80
Option Supplied by External 24VDC requires a power cycle.
8.4.41 ALARM 45, Earth Fault 2
Cause
Ground fault.
Troubleshooting
Check for proper grounding and loose connections.
Check for proper wire size.
Check the motor cables for short circuits or leakage currents.
Danfoss A/S © 2020.01
Maintenance, Diagnostics, and
Troubleshooting
AQ275652274277en-000101 / 130R0708| 115

Advertisement

Table of Contents
loading

Table of Contents