Danfoss VLT AQUA Drive FC 202 Operating Manual page 125

355-800 kw, enclosure sizes e1h-e4h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Operating Guide | VLT® AQUA Drive FC 202
8.4.78 ALARM 82, CSIV Parameter Error
Cause
CSIV failed to initialize a parameter.
8.4.79 ALARM 83, Illegal Option Combination
Cause
The mounted options are incompatible.
8.4.80 ALARM 84, No Safety Option
Cause
The safety option was removed without applying a general reset.
Troubleshooting
Reconnect the safety option.
8.4.81 ALARM 85, Dang Fail PB
Cause
PROFIBUS/PROFIsafe error.
8.4.82 ALARM 88, Option Detection
Cause
A change in the option layout is detected. Parameter 14-89 Option Detection is set to [0] Frozen configuration and the option layout has
been changed.
Troubleshooting
To apply the change, enable option layout changes in parameter 14-89 Option Detection.
Alternatively, restore the correct option configuration.
8.4.83 WARNING 89, Mechanical Brake Sliding
Cause
The hoist brake monitor detects a motor speed exceeding 10 RPM.
Danfoss A/S © 2020.01
Maintenance, Diagnostics, and
Troubleshooting
AQ275652274277en-000101 / 130R0708| 123