Wiring Schematic - Danfoss VLT AQUA Drive FC 202 Operating Manual

355-800 kw, enclosure sizes e1h-e4h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Operating Guide | VLT® AQUA Drive FC 202

5.3 Wiring Schematic

230 V AC
50/60 Hz
3-phase
power
input
Load share
(optional)
+10 V DC
-10 V DC to +10 V DC
0/4-20 mA
-10 V DC to +10 V DC
0/4-20 mA
1 Terminal 37 (optional) is used for Safe Torque Off. Refer to the VLT® FC Series - Safe Torque Off Operating Guide for installation
instructions.
Illustration 18:
Basic Wiring Schematic
40 | Danfoss A/S © 2020.01
TB5
R1
Space heater (optional)
91 (L1)
92 (L2)
93 (L3)
95
PE
88 (-)
power supply
89 (+)
10 V DC
15 mA 200 mA
50 (+10 V OUT)
+
A53 U-I (S201)
53 (A IN)
ON=0/4-20 mA
A54 U-I (S202)
OFF=0 to ±10 V
54 (A IN)
55 (COM A IN)
12 (+24 V OUT)
13 (+24 V OUT)
P 5-00
24 V (NPN)
18 (D IN)
0 V (PNP)
24 V (NPN)
19 (D IN)
0 V (PNP)
20 (COM D IN)
24 V (NPN)
27
(D IN/OUT)
0 V (PNP)
24V
0V
24 V (NPN)
29
(D IN/OUT)
0 V (PNP)
24V
0V
24 V (NPN)
32 (D IN)
0 V (PNP)
24 V (NPN)
33 (D IN)
0 V (PNP)
37 (D IN)
1)
Switch mode
24 V DC
-
+
-
(COM A OUT) 39
S801/Bus Term.
OFF-ON
ON=Terminated
OFF=Open
5V
S801
RS485
(P RS485) 68
interface
(N RS485) 69
(COM RS485) 61
Electrical Installation
(U) 96
(V) 97
(W) 98
(PE) 99
Motor
Regen +
Brake
(R+) 82
resistor
(optional)
Regen (optional)
(R-) 81
Regen -
83
Relay1
03
240 V AC, 2A
02
400 V AC, 2A
01
Relay2
06
240 V AC, 2A
05
400 V AC, 2A
04
Analog output
0/4-20 mA
(A OUT) 42
1
Brake temperature
(NC)
2
0V
RS485
(PNP) = Source
(NPN) = Sink
AQ275652274277en-000101 / 130R0708

Advertisement

Table of Contents
loading