Danfoss VLT AQUA Drive FC 202 Operating Manual page 133

355-800 kw, enclosure sizes e1h-e4h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Operating Guide | VLT® AQUA Drive FC 202
FC 202
Efficiency
(3)
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Power card overtemperature trip [°C (°F)]
Fan power card overtemperature trip [°C (°F)]
Active in-rush card overtemperature trip [°C (°F)]
9.7 Fuses
1
For fuse ratings, see
.
2
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor
efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default
setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/
vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see
Conditions
. For part load losses, see www.danfoss.com/vltenergyefficiency.
Table 46: Electrical Data, Mains Supply 3x380–480 V AC
FC 202
High/normal overloadHigh overload=150% or 160% torque for a duration of 60 s.
Normal overload=110% torque for a duration of 60 s.
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Typical shaft output at 480 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 400 V) [A]
Intermittent (60 s overload) (at 400 V) [A]
Continuous (at 460/480 V) [A]
Intermittent (60 s overload) (at 460/480 V) [A]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Continuous kVA (at 480 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460/480 V) [A]
Maximum number and size of cables per phase (E2h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
Danfoss A/S © 2020.01
2
(AWG)]
2
(AWG)]
N355
N400
0.98
0.98
0–590
0–590
110 (230)
110 (230)
80 (176)
80 (176)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
N500
HO
450
600
530
E2h/E4h
800
1200
730
1095
554
582
607
771
704
6x240 (6x500 mcm)
5x240 (4x500 mcm)
AQ275652274277en-000101 / 130R0708| 131
Specifications
N450
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
9.4 Ambient
N560
NO
HO
NO
500
500
560
650
650
750
560
560
630
E2h/E4h
880
880
990
968
1320
1089
780
780
890
858
1170
979
610
610
686
621
621
709
648
648
740
848
848
954
752
752
858
6x240 (6x500 mcm)
5x240 (4x500 mcm)