9.6.8 Control Card, 24 V DC Output

Terminal number
Maximum load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs
and outputs.

9.6.9 Relay Outputs

Programmable relay outputs
Maximum wire cross-section to relay terminals
Minimum wire cross-section to relay terminals
Length of stripped wire
Relay 01 terminal number
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Minimum terminal load on 1–3 (NC), 1–2 (NO)
Environment according to EN 60664-1
Relay 02 terminal number
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Minimum terminal load on 4–6 (NC), 4–5 (NO)
Environment according to EN 60664-1
1
IEC 60947 parts 4 and 5.
2
Overvoltage Category II
3
UL applications 300 V AC 2 A.
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
140 | Danfoss A/S © 2020.01
(1)
on 1–2 (NO) (Resistive load)
(1)
1–2 (NO) (Inductive load @ cosφ 0.4)
(1)
on 1–2 (NO) (Resistive load)
(1)
on 1–2 (NO) (Inductive load)
(1)
on 1–3 (NC) (Resistive load)
(1)
1–3 (NC) (Inductive load @ cosφ 0.4)
(1)
on 1–3 (NC) (Resistive load)
(1)
on 1–3 (NC) (Inductive load)
(1)
on 4–5 (NO) (Resistive load)
(1)
4–5 (NO) (Inductive load @ cosφ 0.4)
(1)
on 4–5 (NO) (Resistive load)
(1)
on 4–5 (NO) (Inductive load)
(1)
on 4–6 (NC) (Resistive load)
(1)
4–6 (NC) (Inductive load @ cosφ 0.4)
(1)
on 4–6 (NC) (Resistive load)
(1)
on 4–6 (NC) (Inductive load)
(2) (3)
(2) (3)
Specifications
2.5 mm
0.2 mm
1–3 (break), 1–2 (make)
24 V DC 10 mA, 24 V AC 2 mA
Overvoltage category III/pollution degree 2
4–6 (break), 4–5 (make)
24 V DC 10 mA, 24 V AC 2 mA
Overvoltage category III/pollution degree 2
AQ275652274277en-000101 / 130R0708
12, 13
200 mA
2
2
(12 AWG)
2
(30 AWG)
8 mm (0.3 in)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
50 V DC, 2 A
24 V DC, 0.1 A
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
50 V DC, 2 A
24 V DC, 0.1 A