Operating Guide | VLT® AQUA Drive FC 202
Parameter settings
Table 36: Relevant Parameters for Submersible Pump Application
Parameter
Parameter 1-20 Motor Power [kW]/parameter 1-21 Motor Power [HP]
Parameter 1-22 Motor Voltage
Parameter 1-24 Motor Current
Parameter 1-28 Motor Rotation Check
Parameter 1-29 Automatic Motor Adaptation (AMA) = [2] Enable Reduced AMA
Table 37: Example of Settings for Submersible Pump
Parameter
Parameter 3-02 Minimum Reference
Parameter 3-03 Maximum Reference
Parameter 3-84 Initial Ramp Time
Parameter 3-88 Final Ramp Time
Parameter 3-41 Ramp 1 Ramp Up Time
Parameter 3-42 Ramp 1 Ramp Down Time
Parameter 4-11 Motor Speed Low Limit [RPM]
Parameter 4-13 Motor Speed High Limit [RPM]
To set up the feedback settings in the PID controller, use the Closed-loop wizard under Quick Menu, Function Set-up.
Table 38: Example of Settings for Pipe-Fill Mode
Parameter
Parameter 29-00 Pipe Fill Enable
Parameter 29-04 Pipe Fill Rate
Parameter 29-05 Filled Setpoint
Danfoss A/S © 2020.01
Setting
The minimum reference unit matches the unit in parameter 20-12 Reference/ Feed-
back Unit
The maximum reference unit matches the unit in parameter 20-12 Reference/ Feed-
back Unit
(2 s)
(2 s)
(8 s depending on size)
(8 s depending on size)
(30 Hz)
(50/60 Hz)
Wiring Configuration Examples
Setting
Disabled
(Feedback units)
(Feedback units)
AQ275652274277en-000101 / 130R0708| 93