COMTRAXX® CP305 - Control Panel
Remote alarm indicator for medical locations and other areas
CP305_D00425_02_M_XXEN/07.2023

Advertisement

Table of Contents
loading

Summary of Contents for Bender COMTRAXX CP305

  • Page 1 Manual EN COMTRAXX® CP305 - Control Panel Remote alarm indicator for medical locations and other areas CP305_D00425_02_M_XXEN/07.2023...
  • Page 2 CP305_D00425_02_M_XXEN/07.2023...
  • Page 3: Table Of Contents

    Indication of important instructions and information...............6 Signs and symbols............................6 Service and Support............................6 Training courses and seminars........................6 Delivery conditions............................7 Inspection, transport and storage......................7 Warranty and liability.............................7 Disposal of Bender devices..........................7 1.10 Safety..................................8 Intended use....................... 9 Product description..................10 Scope of delivery............................10 Device features...............................10 System description............................
  • Page 4 Table of contents Display and operation..................29 Display CP305: Menu structure...............31 10.1 Measured values............................31 10.2 Bus overview..............................31 10.3 History................................31 10.4 Alarm and test..............................33 10.5 Settings................................33 10.6 Info..................................37 Web user interface: menu structure (via ETH socket)........38 11.1 COMTRAXX ®...
  • Page 5 COMTRAXX® CP305 - Control Panel 12.10 Service inspection............................48 12.11 Factory setting..............................49 Web user interface: Menu structure (access via gateway)......50 13.1 Device tools..............................50 13.2 Menu.................................. 50 13.2.1 Edit texts................................50 13.2.2 Info..................................51 Export and import of device data..............52 Cleaning, servicing and troubleshooting............53 15.1 Cleaning................................
  • Page 6: General Information

    Recycling RoHS directives Service and Support Information and contact details about customer service, repair service or field service for Bender devices are available on the following website: Fast assistance | Bender GmbH & Co. KG. Training courses and seminars Regular face-to-face or online seminars for customers and other interested parties: www.bender.de >...
  • Page 7: Delivery Conditions

    COMTRAXX® CP305 - Control Panel Delivery conditions The conditions of sale and delivery set out by Bender GmbH & Co. KG apply. These can be obtained in printed or electronic format. The following applies to software products: ‘Software clause in respect of the licensing of standard software as part of deliveries,...
  • Page 8: Safety

    General information 1.10 Safety If the device is used outside the Federal Republic of Germany, the applicable local standards and regulations must be complied with. In Europe, the European standard EN 50110 applies. DANGER Risk of fatal injury due to electric shock! Touching live parts of the system carries the risk of: •...
  • Page 9: Intended Use

    COMTRAXX® CP305 - Control Panel Intended use Remote alarm indicator COMTRAXX ® CP305 is used for visual and audible signalling of operating and alarm messages from the Bender systems MEDICS ® , ATICS ® , EDS and RCMS. In MEDICS ®...
  • Page 10: Product Description

    • Connection plug kit (power supply, RS485 connection) • Connections for the digital inputs and relay outputs • A printed quick reference guide The manuals are available at: https://www.bender.de/en/service-support/download-area/ • Safety instructions for Bender products Installation options • Flush-mounting (flush-mounting enclosure B923710) •...
  • Page 11: System Description

    • History memory with real-time clock to store 1000 warnings and alarms • Power supply via power supply unit • Parameter setting via Ethernet interface • NFC interface for connection to the Bender Connect app • Replacing MK2430 (retrofit); other devices on request Applications •...
  • Page 12: Interfaces

    Connection example BMS and Ethernet In the example, the ICU can be monitored from the station base. In addition, remote maintenance is possible via the building services or Bender. Interfaces The BMS bus is used for communication with BMS bus nodes or devices like RCMS…, EDS…, SMI…, SMO…, ATICS ®...
  • Page 13 The powered device can also have its parameters set via NFC. The interface is activated on the CP305 under > Settings > Interface > NFC. Afterwards, the prepared configuration can be loaded onto the device using the Bender Connect app. CP305_D00425_02_M_XXEN/07.2023...
  • Page 14: Mounting

    Mounting Mounting Dimension diagram CP305 All dimensions are in mm. Flush-mounting The flush-mounting enclosure is optionally available (B923710). CP305_D00425_02_M_XXEN/07.2023...
  • Page 15 COMTRAXX® CP305 - Control Panel Dimension diagram flush-mounting enclosure All dimensions are in mm. CP305_D00425_02_M_XXEN/07.2023...
  • Page 16 Mounting Installation of flush-mounting enclosure Insert the supplied cardboard into the flush-mounting enclosure to provide protection against pollution. Insert the enclosure so that it is flush with the wall surface. The flush-mounting enclosure must not be installed lopsidedly or warped, and must not be installed too deep below the surface.
  • Page 17: Surface Mounting

    COMTRAXX® CP305 - Control Panel Surface mounting For surface mounting, the matching surface-mounting enclosure (item no. B95100153) must be used. All dimensions are in mm. 100.5 185.5 Cavity wall and panel mounting For cavity wall or panel mounting, you need the “Cavity wall mounting set” (item no. B923711). Cavity wall mounting Panel mounting CP305_D00425_02_M_XXEN/07.2023...
  • Page 18: Retrofit: Replacement Of Mk2430

    In the context of retrofit measures, CP305 can be installed directly in the existing flush-mounting MK2430 enclosures. If MK2418, MK2410 or other devices are to be replaced, the flush-mounting enclosures must be changed. Please contact Bender Service for details. CP305_D00425_02_M_XXEN/07.2023...
  • Page 19: Connection

    COMTRAXX® CP305 - Control Panel Connection Safety instructions Only skilled persons are permitted to carry out the work necessary to install, put into service and run a device or system. DANGER Danger of electric shock! Follow the basic safety rules when working with electricity. Observe the information on rated voltage and supply voltage specified in the technical data! DANGER Connect the CP305 exclusively according to the connection diagram in this chapter.
  • Page 20 Connection Notes on the connection Supply voltage – Connect the CP305 devices to the supply voltage (terminals A1/+, A2/–). • DC 24 V: Take the line voltage drop into account if you are using long supply cables for the supply voltage.
  • Page 21: Connection Diagram

    COMTRAXX® CP305 - Control Panel Connection diagram GND 1-4 K2 NO IN 1 K2 NC IN 2 K2 COM IN 3 IN 4 K1 NO GND 5-8 K1 NC IN 5 K1 COM CP305-IO IN 6 BMS A IN 7 BMS B IN 8 Term = on...
  • Page 22 IN1…12. Ethernet interface for connection of a PC The CP305 can be integrated into the Bender/hospital network via the Ethernet interface. Parameters can be set on the PC, and data as well as the history memory can be read out. Connected measuring devices can be displayed with their channels.
  • Page 23: Ethernet Connection

    COMTRAXX® CP305 - Control Panel Connection assignment (rear) The connections are located on the back of the device. The dip switch for terminating the BMS bus is located on the bottom of the device: CP305 IN 8 K2 COM IN 7 K2 NC IN 6 K2 NO...
  • Page 24 Connection Operating mode digital inputs The choices are “off”, “High-active”, “Low-active”. High-active (N/C) Low-active (N/O) An event is executed when the digital input An event is executed when the digital input experiences an edge change from low to high. experiences an edge change from high to low. Response time t(on)/t(off) after a switch-on signal.
  • Page 25: Commissioning

    COMTRAXX® CP305 - Control Panel Commissioning Commissioning assistant During initial putting into service or after a reset to factory settings, the putting-into-service wizard opens for the basic setup steps. The putting-into-service wizard launches in English. The header is blue, and the LED is green. You need to log in to the device (with the PIN via the icon in the header).
  • Page 26 The NFC interface can be used to transmit a previously configured device parameter setting directly to the device. This function is available only via the Bender Connect App. You can find this app in the Appstores for iOS and Android.
  • Page 27: Software Update

    It is recommended to create a backup before an update. Download the current software version from the Bender homepage and save it to your PC. Now connect the CP305 to the PC. The parameterised IP address of the CP305 can be found in the device menu under Info.
  • Page 28: Factory Settings For Communication

    Factory settings for communication Factory settings for communication The settings can be changed on the device or via the web user interface. Parameter Parameter IP address IP address for 1:1 ETH connection Address range (169.254.xx.yy) Note: xx and yy are derived from the MAC address during putting into service and are therefore unique for each CP305.
  • Page 29: Display And Operation

    COMTRAXX® CP305 - Control Panel Display and operation Operation with latex, vinyl and nitrile gloves is possible without restricting functionality. LED and display Display in normal operation: There are no warnings or alarms pending. • The LED lights up green. •...
  • Page 30 Display and operation Footer Timer • Setting range: 1 s to (10 h - 1 s) Resolution of setting 1 s • A timer can be set and started on the default display screen. It counts down to 0 and signals the elapsed time interval with its buzzer.
  • Page 31: Display Cp305: Menu Structure

    COMTRAXX® CP305 - Control Panel Display CP305: Menu structure Normal state: The header and the LED are green when there is no alarm. In the event of an alarm, the header and LED take on the colour of the highest alarm level present. 10.1 Measured values •...
  • Page 32 Display CP305: Menu structure Detail pop-up of an entry in the history Element Comments Messages that come up are indicated in different colours, depending on their type, both on the display and in the stored history. Warnings: yellow Error category Alarms: red Warning end, alarm end: green Device error...
  • Page 33: Alarm And Test

    COMTRAXX® CP305 - Control Panel 10.4 Alarm and test Alarm addresses Display of the addresses/measuring channels whose alarm messages are assigned to the CP305. The following are shown: • BMS address/channel • Device name • Path to the alarm value •...
  • Page 34 Display CP305: Menu structure t(off) • The switch-off delay indicates how long an alarm needs to no longer be present before the message is also cancelled. • Setting range 0…600 s Relays Carry out operating principle and function for relays 1…2. •...
  • Page 35 COMTRAXX® CP305 - Control Panel Date and time Setting option for • Time, date, time zone, daylight saving time • Synchronisation with time server (SNTP) (auto DHCP, on, off) Display General • Language • Alignment • Cleaning mode active Setting option: deactivated or locked for 5…20 s Alarm messages •...
  • Page 36 Display CP305: Menu structure Server • Administrator User name (display only) Status (enabled, disabled) Password (only *** is shown) Read access (allow) Write access (allow) • User User name (display only) Status (enabled, disabled) Password (only *** is shown) Read access (display only) Write access (display only) •...
  • Page 37: Info

    COMTRAXX® CP305 - Control Panel For the service inspection, it is necessary to first create at least one alarm address. Factory setting Restart device (Execute) The device can be reset with or without interface settings. • With interface: The device is reset to factory settings, and individual interface settings are discarded. •...
  • Page 38: Web User Interface: Menu Structure (Via Eth Socket)

    11.1 COMTRAXX ® user interface 11.1.1 Header Element Description Click the logo: Return to the start page Bender CP305 Device used: Device type COMTRAXX ® System x y Device used: System name > Subsystem > Device address 2023-01-16 Date and time of the device 09:47 (+01:00) The icon shows that the web user interface is protected by a password.
  • Page 39: Navigation

    COMTRAXX® CP305 - Control Panel Element Description Open/close the navigation (button only available with small browser window) If you have forgotten the password, the Bender service can generate a one-time password. Have your serial number ready for this. 11.1.2 Navigation Menu...
  • Page 40: Alarm Overview (Footer)

    Web user interface: menu structure (via ETH socket) 11.1.5 Alarm overview (footer) Overview of pending alarms Click the alarm overview: List of pending alarms Click the list: Details of the alarms in the content section History memory of the device From the alarm overview, you can jump directly to the stored history of the CP305.
  • Page 41: Menu

    COMTRAXX® CP305 - Control Panel Import backup You can import an existing backup here. All information in the backup is compared with the current information on the device. Then you can select the ones you want to import. Important: Please ensure in advance that the backup file is intended for the device! You switch to the next step by pressing the “Next”...
  • Page 42: Tools

    Web user interface: menu structure (via ETH socket) 11.5 Tools 11.5.1 Monitoring 11.5.1.1 Device failure monitoring All devices whose failure is monitored are summarised here in a list. The CP305 can generate messages when a device on the BMS bus fails. To do this, the device must be included in the list of devices to be monitored.
  • Page 43: Device Management

    COMTRAXX® CP305 - Control Panel Footer • Import: Import configuration file of the alarm addresses (Excel file). * • Export: Export configuration file of the alarm addresses (Excel file) • Import ACTUAL state • Save changes • Discard changes • Add entry * Only configuration files that were previously exported from CP305 can be imported.
  • Page 44: Service

    Important note: Search for a device can briefly cause considerable data traffic on the network. 11.5.3.3 Log files Log files are saved as txt files. In the event of a fault, log files help Bender Service to more easily find the cause. 11.5.3.4 Device restart The CP305 can be restarted from the web user interface without it being necessary to disconnect the CP305 from the power supply.
  • Page 45: Web User Interface: Settings (Via Eth Socket)

    COMTRAXX® CP305 - Control Panel Web user interface: Settings (via ETH socket) You need to save the changes before you quit the respective screen. Otherwise, the changes will be discarded. 12.1 Digital inputs 1-12 Menu > Settings > Digital Input 1 - 12 For each of the 12 digital inputs IN1…12 can be set: Adjustable Parameter...
  • Page 46: Relays 1-2

    Web user interface: Settings (via ETH socket) 12.2 Relays 1-2 Menu > Settings > Relay Carry out operating principle and function for relays 1…2. Operating principle Function Alarm addresses Buzzer Normally open / Normally closed Alarm addresses | Buzzer Test Isometer •...
  • Page 47: History

    COMTRAXX® CP305 - Control Panel Device Configure the displayed device name. Saved changes are immediately applied to the CP305. The individual device name is appended to the device type in the history. Example: Device name “Room 4.2.3 Window” is listed in the history as “CP305-IO – Room 4.2.3 Window”. You do not need to include the device type here.
  • Page 48: Buzzer

    Web user interface: Settings (via ETH socket) Display The PIN for logging in to the device consists of 4 digits. The factory setting is "8070". • PIN (enabled/disabled) • PIN (change PIN) Server The password for the web user interface is alphanumeric. The factory setting is "admin".
  • Page 49: Factory Setting

    COMTRAXX® CP305 - Control Panel Prewarning (deactivated, 1 week … 3 months) – message before the service interval expires so that plans can be made for the next inspection. Next service (display only) Service inspection Next service Only displayed when a service interval is set. Last service Date display on which date the last service check was carried out.
  • Page 50: Web User Interface: Menu Structure (Access Via Gateway)

    Web user interface: Menu structure (access via gateway) Web user interface: Menu structure (access via gateway) If the CP305 is connected to a CP9xx control panel or a COM465 gateway or the like, a device menu of the CP305 can be opened. This can be used to call up device information. 13.1 Device tools Device tools...
  • Page 51: Info

    COMTRAXX® CP305 - Control Panel Channel 1 - 12 For each of the channels 1…12 (digital inputs), custom message texts can be assigned for: • Description • Warning • Prewarning 13.2.2 Info Display of • Device type • Software • producer •...
  • Page 52: Export And Import Of Device Data

    Export and import of device data Export and import of device data Different device data can be exported via the web user interface. They are exported in the appropriate format depending on the application. You will find the files in the Download folder of your computer. Likewise, these files can also be imported back into the CP305 (except pdf).
  • Page 53: Cleaning, Servicing And Troubleshooting

    COMTRAXX® CP305 - Control Panel Cleaning, servicing and troubleshooting 15.1 Cleaning The glass front can be wiped clean with common cleaning agents. The glass and seal are resistant to alcohol- based disinfectants. 15.2 Servicing The device does not contain any parts that require servicing. Despite this, the intervals specified for periodic verification should be adhered to.
  • Page 54: Malfunctions

    “neutral/medical”. 15.6 Recurring inspections The following periodic verification must be performed on electrical installations in compliance with the local or national regulations that apply. For your Bender products, we recommend: Action Carried out by Interval Functional test of the IT system monitoring (insulation, load current, transformer Med.
  • Page 55 Action Carried out by Interval Test the changeover device, the IT system monitoring, and the connection to the Bender Every 24 SCADA system (Supervisory Control and Data Acquisition) (if applicable) as well as months the interaction between the components in the system.
  • Page 56: Technical Data

    Technical data Technical data The CP305 is intended for use in basic (DIN EN 61326-1, Table 1) and industrial (DIN EN 61326-1, Table 2) electromagnetic environments. 16.1 Tabular data ()* = factory setting Insulation coordination CP305 acc. to IEC 60664-1 Rated voltage 50 V Overvoltage category...
  • Page 57 COMTRAXX® CP305 - Control Panel Displays, memory Number of history memory entries 1000 Interfaces Ethernet Connection RJ45 Data rate 10/100 Mbit/s, autodetect DHCP on/off (on)* IP address (1:1 connection) 169.254.xx.yy (xx and yy are unique for each device) Netmask nnn.nnn.nnn.nnn (255.255.255.0)* Logs TCP/IP, Modbus TCP, DHCP, SNTP Modbus TCP...
  • Page 58 Technical data Digital inputs (1…12) Factory setting Voltage range (high) AC/DC 10…30 V Nominal: 24 V Voltage range (low) AC/DC 0…2 V Max. current per channel (at AC/DC 30 V) 8 mA Connection Plug-in terminals IN 1… 4 / GND1-4 IN 5…8 / GND 5-8 IN 9…12 / GND 9-12 Maximum cable length...
  • Page 59 COMTRAXX® CP305 - Control Panel Device connections Plug-in terminal (A1/+, A2/-) Conductor sizes AWG 24…12 Stripping length 10 mm Rigid/flexible 0.2…2.5 mm² Flexible with ferrules, with/without plastic sleeve 0.25…2.5 mm² Multiple conductor flexible with TWIN ferrule with plastic 0.5… 1.5 mm² sleeve Plug-in terminals (BMS A, BMS B), (IN1…4, GND1…4, IN9…12, GND9…12) (IN5…8, GND5…8, K1…, K2…)
  • Page 60: Standards And Approvals

    Technical data Classification of climatic conditions acc. to IEC 60721 Stationary use (IEC 60721-3-3) 3K22 Transport (IEC 60721-3-2) 2K11 Long-term storage (IEC 60721-3-1) 1K22 Classification of mechanical conditions acc. to IEC 60721 Stationary use (IEC 60721-3-3) 3M11 Transport (IEC 60721-3-2) Long-term storage (IEC 60721-3-1) 1M12 Other...
  • Page 61: Document Revision History

    COMTRAXX® CP305 - Control Panel Accessories Type Description Art.-No. Flush-mounting enclosure B923710 Cavity wall installation set for flush- Installation set for flush-mounting B923711 mounting enclosure enclosure B923710 CP305 surface-mounting enclosure B95100153 CP305-IO plug kit CP305-IO connector kit B95100151 Ethernet adapter kit (RJ45 socket Ethernet connector kit B95100152 insert, Cat.6 SLIM patch cable)
  • Page 62: Eu Declaration Of Conformity

    EU Declaration of Conformity EU Declaration of Conformity Bender GmbH & Co. KG hereby declares that the device covered by the Radio Directive complies with Directive 2014/53/EU. The full text of the EU Declaration of Conformity is available at the following Internet address: https://www.bender.de/fileadmin/content/Products/CE/CEKO_CP3xx.pdf...
  • Page 63 COMTRAXX® CP305 - Control Panel CP305_D00425_02_M_XXEN/07.2023...
  • Page 64 Alle Rechte vorbehalten. 35305 Grünberg Nachdruck und Vervielfältigung nur mit Germany Genehmigung des Herausgebers. © Bender GmbH & Co. KG, Germany Subject to change! The specified Tel.: +49 6401 807-0 All rights reserved. standards take into account the edition info@bender.de Reprinting and duplicating only with valid until 07.2023 unless otherwise...