ABB AC500 PLC Hardware Manual page 68

Table of Contents

Advertisement

Device Specifications
Processor Modules > AC500 (Standard)
1.2.2.1.2
Assortment
Module
Program
and Data
Memory
PM572
128 kB
PM573-ETH 512 kB
PM582
512 kB
PM583-ETH 1 MB
PM585-ETH 1 MB
PM590-ETH
2 MB
1
(
)
PM590-
2 MB
ARCNET
(R0261)
PM591-ETH 4 MB
PM591-ETH 4 MB
PM591-2ET
4 MB
H
PM592-ETH 4 MB
Remarks:
1
): The processor modules PM59x-ETH can only be used with terminal bases with product index
C6 or higher. Otherwise, they should be updated to that index.
on page 4
2
): Serial interface COM1, Communication Interface Module, I/O bus
3
): Serial interface COM1, Serial interface COM1, Communication Interface Module, FieldBus-
Plug (FBP), I/O bus
68
Cycle Time
Network Interface
for 1 Instruc-
Ethernet
tion
Binary: min.
-
0.06 µs
Onboard
Word: min.
Ethernet
0.09 µs
Floating point:
min. 0.70 µs
Binary: min.
-
0.05 µs
Onboard
Word: min.
Ethernet
0.06 µs
Floating point:
min. 0.50 µs
Binary: min.
Integrated com-
0.002 µs
munication
module
Word: min.
0.004 µs
Floating point:
min. 0.004 µs
-
-
-
Integrated com-
munication
module
-
Onboard
Ethernet
-
2x Onboard
Ethernet
Onboard
Ethernet
Processor modules PM57x-ETH, PM58x-ETH and PM59x-ETH with ordering
No. 1SAPxxxxxxR0271 can only be used with terminal bases with ordering No.
1SAPxxxxxxR0270.
Processor modules PM5xx-2ETH can only be used with TB5x3-2ETH terminal
bases.
3ADR010121, 13, en_US
Other Inter-
faces
ARCNET
-
3
)
-
3
)
-
3
)
-
3
)
3
)
-
3
)
Integrated
3
)
communication
module
-
3
)
-
3
)
-
2
)
-
3
)
Ä Chapter 1.1.1 "TB51x-TB54x"
Suitable
Terminal Base
TB5x1-ETH
TB5x1-ETH
(1SAP11x100R0
270 only)
TB5x1-ETH
TB5x1-ETH
(1SAP11x100R0
270 only)
TB5x1-ETH
TB5x1-ARCNET
TB5x1-ETH
TB5x1-ETH
(1SAP11x100R0
270 only)
TB5x3-2ETH
TB5x1-ETH
(1SAP11x100R0
270 only)
2019/04/17

Advertisement

Chapters

Table of Contents
loading

Table of Contents