The communication between the processor module and the communication modules takes
place via the communication module bus, which is integrated in the terminal base. Depending
on the used Terminal Base, 1, 2 or 4 communication modules can be connected.
There are no restrictions concerning which communication modules can be arranged for a pro-
cessor module.
The communication modules can be used as
bus master or
slave
within the AC500 control system.
It depends on the
selected protocol,
the functionality of the communication module and
the several field buses and networks.
The following name extensions of the device names describe the supported field bus/protocol:
CMxyz-ETH: Ethernet
CMxyz-DP: PROFIBUS
CMxyz-PNIO: PROFINET
CMxyz-ETHCAT: EtherCAT
CMxyz-CN: CANopen
CMxyz-RCOM: RCOM/RCOM+ protocol (and 2 serial interfaces)
CMxyz-RS: 2 serial interfaces (COM1/COM2)
If a XC version of the device is available, for use in extreme ambient conditions (e.g. wider tem-
perature and humidity range), this is indicated with a snowflake sign.
2019/04/17
WARNING!
Removal/Insertion under power
The devices are not designed for removal or insertion under power. Because of
unforeseeable consequences, it is not allowed to plug or unplug devices with
the power being ON.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
connect or disconnect any signal or terminal block
remove, mount or replace a module.
Disconnecting any powered devices while energized in a hazardous location
could result in an electric arc, which could create a flammable ignition resulting
in fire or explosion.
Make sure that power is removed and that the area has been thoroughly
checked to ensure that flammable materials are not present prior to proceeding.
The devices must not be opened when in operation. The same applies to the
network interfaces.
For information on mounting, disassembling and electrical connection, please
refer to System Assembly
3ADR010121, 13, en_US
Communication Modules (AC500 Standard) > Overview
Device Specifications
93