Premium Delayed Egress
PED4000 D, PED5000 D Series Exit Device
Installation Instructions
14
Operating Instructions, continued
Re-arm After Closing for Indefinite Delay
With 40 second momentary egress setting (S2-4 ON & S2-5 ON), S2-7 ON, and an external DPS is wired to the PCBA (S2-8
OFF), after activation of momentary egress by cylinder key switch or external remote reset signal, if the Door/DPS is open
beyond 40 seconds, it will remain in momentary egress mode indefinitely and shall not enter alarm mode. Then once the
Door/DPS is closed, it will re-arm immediately. With (S2-4 ON & S2-5 ON) S2-8 OFF and S2-7 OFF for same scenario as above,
the device will enter alarm mode after 40 seconds if the Door/DPS is still open. If Door/DPS is closed before 40 seconds, it will
re-arm immediately.
15

Additional Options Non ElectroLynx Wiring

Electrically Controlled ET Trim "Safe/Secure"
The Delayed Egress Exit Device is available with Fail Safe (SAF) or Fail Secure (SEC) outside trim operation. In a fire
condition, the Fail Safe trim will release for entry. When Access control is used, the Fail Secure trim allows entry by
means of a remote card reader, keyswitch, push button, etc.
Note: If a Door Position Switch is not used, the trim will open the door without affecting the device in an armed
condition (refer to wiring diagrams for wiring).
Note: If an external DPS is not used, Standard trim and Safe/Secure trim will allow entry without affecting the device in
an armed mode. The device will only be affected when the push pad is depressed (refer to wiring diagrams for wiring).
16
BOCA 15 Second Delay BC-59_ and BOCA 30 Second Delay BC-59_
Upon depressing the pushpad for 1 second or longer, the device will sound an audible continuous tone and allow the
door to be opened within 15 (or 30) seconds. The alarm will remain as a continuous tone until reset. Resetting of the
alarm and re-arming of the device occurs automatically once the door has been returned to the closed position for 30
seconds. The 30-second re-arming timer will re-start if the pushpad is depressed or the door is re-opened before actual
re-arming of the device occurs. A DPS (Door Position Switch) is required for the BOCA option.
NOTE: BOCA option is not suitable for installations in accordance with NFPA 101.
17
NFPA 101 Requirements: 30 Second Delay BC-59_ Suffix
Upon depressing the pushpad for 3 seconds or longer, the device will sound an audible continuous tone and allow the
door to be opened after 30 seconds. The alarm will remain as a continous tone until reset. Resetting of the alarm and
re-arming of the device is accomplished by manual means only.
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without
the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
34
FM574 01/23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Corbin russwin ped4000 d series

Table of Contents