Premium Delayed Egress
PED4000 D, PED5000 D Series Exit Device
Installation Instructions
8
Input and Output Connector Designations, Continued
Harness
I/O Circuit
Connector
Board Pin
Pin Number*
Number
8-2
J200-2
8-1
J200-1
8-3
J200-4
8-4
Chassis Ground Chassis Ground - The chassis ground wire must terminate at earth ground of the
8-5
J200-6
8-6
J200-8
8-7
J200-5
8-8
J200-9
4-1
J200-12
4-2
J200-14
4-3
J200-11
4-4
J200-13
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without
the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
Function
+24 VDC Power Supply Input (+) - This input may be tied to the normally closed
contact of a building's fire alarm system. If the fire alarm is activated, this contact
will open, voiding the15 second delay for egress.
Return - Power Supply -return (-)
Remote Reset - This input may be tied to a momentary normally open contact
at a remote location to reset the device when in alarm. Additionally when the
device is armed, this input may be used for momentary egress with the time per
the dip switch settings.
NOTE: Previous Fire Alarm Input option has been replaced with Remote Reset.
equipment power supply or the main power source.
External inhibit Input - Used to provide remote override of the delayed egress
when in the armed condition. Most common external inhibits are: key switches,
card readers, keypad, or remote control console. More than one external inhibit
device must be wired in parallel
Door position sensor - An external door status switch can be connected to the
DEED to provide additional security. If the door status switch is utilized, an irre-
versible alarm will sound if the door is forced open while the device is armed. Unit
will not arm if door is not shut. Once the irreversible alarm sounds, it will have to
be reset at the door. If the door status switch is not utilized, set
DIP Switch S2-8 to the ON position.
Remote Alarm Relay - A SPDT (Single Pole Double Throw) 1A, 24 VDC contact
relay is provided for external alarm indication. The contacts change state when
the unit goes into an irreversible alarm or if the door is forced open while the
device is armed. A door position sensor is required for monitoring a door forced
open condition. This contact can be utilized to drive a horn, lamp or other
monitoring device.
ET- and ET+ - Electrified Exit Trim (Fail Safe or Fail Secure) can be used for
authorized ingress (via card reader, keypad, and other switches).
SEC-C and SEC-NO: SPDT (Single Pole Double Throw) -1A, 24VDC relay. Secure
(SEC) relay changes state after 15 or 30 second delayed egress delay.
24
FM574 01/23