Premium Delayed Egress
PED4000 D, PED5000 D Series Exit Device
Installation Instructions
3
DIP Switch Settings, continued
Nuisance Delay (seconds)
0
1
2
S2-2
OFF
OFF ON
S2-3
OFF
ON
OFF
Reset Delay (seconds)
5
10
20
S2-4
OFF
OFF ON
S2-5
OFF
ON
OFF
Default
*With S2-7 OFF (S2-4 and S2-5 set for 5, 10, 20 or 40sec), if door/DPS is open after selected time the alarm will sound. Close door to
reset and rearm device using cylinder key or remote reset signal.
**S2-7: When an external DPS is used and switch S2-7 ON, and 40 second reset delay (S2-4 and S2-5) are set ON, after activation of
momentary egress by cylinder key switch or external remote reset signal, if the Door/DPS is open beyond 40sec the device will remain
in momentary egress mode indefinitely and shall not enter alarm mode; then once the Door/DPS is closed it will rearm immediately.
If door/DPS is opened then closed before selected time expires, the device will rearm immediately.
If DPS is not used, is bypassed with S2-8 ON, the door will rearm immediately after 5, 10, 20 or 40 sec whether the door is open or
closed, with either S2-7 ON or OFF.
Ensure eight S2 Dip Switches are set per application before moving on to the next page of instructions .
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without
the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
S2-6
OFF
Cover Armed LED Color is Green
3
ON
Cover Armed LED Color is Red (default)
ON
S2-7
OFF*
Momentary egress mode 5, 10, 20 or 40 seconds. Device will immediately
ON
Rearm After Closing (RAC) door, if closed before selected time expires or
it will enter alarm mode, if time expires with door open (default).
See other details*
40
ON**
40 seconds momentary egress mode is extended indefinitely, if the door
ON
is left open. Then the device immediately Rearms after Closing (RAC)
door. See other details**
ON
S2-8
OFF
External DPS is wired to device
ON
DPS Bypass, external DPS is NOT wired to device
7
default
(
)
FM574 01/23