Premium Delayed Egress
PED4000 D, PED5000 D Series Exit Device
Installation Instructions
14

Operating Instructions

There are three (3) modes of operation (Figure 12):
• Delayed Egress
• Momentary Egress
• Bypass (Maintained) Egress
Delayed Egress Mode
1.
Apply power to device. The initialization / self test sequence is as follows:
Cover LED is GREEN for 2 seconds with horn sounding for 500ms.
Cover LED is then RED for 2 seconds, followed by AMBER for 2 seconds with the 4 diagnositc LEDs illuminated.
Cover LED is RED or GREEN (based on the setting of the Armed LED Color DIP Switch Position 6) and green diagnostic LED
is illuminated. The device is now armed, which will not allow pushpad to retract latchbolt for immediate egress.
2.
If the device is not functioning, refer to the Troubleshooting Guide.
Momentary Egress Mode (Figure 12)
1.
With device armed, rotate key counter clockwise and return to center position (remove key).
2.
Red LED (or LED color opposite the Armed LED Color Setting per DIP Switch Position 6) will flash quickly. Device will
release for momentary egress for 10 seconds (factory set). 5, 10, 20, or 40 second reset delay may be selected using DIP
Switch positions 4 and 5.
3.
After the reset delay time has elapsed, or if the cylinder key is rotated a second time counter clockwise while the door/
DPS is closed during a reset delay, the device shall re-arm. When an external DPS is used and (DIP Switch position 7 is
off) door is opened and closed during momentary egress, the selected reset delay shall be canceled and the device shall
re-arm.
4.
Device will now be back in delayed egress mode.
Bypass (Maintained) Egress Mode (Figure 12)
1.
Rotate key clockwise, return key to center position and remove.
2.
Cover LED is solid GREEN (default) or LED color opposite the Armed LED Color Setting per DIP Switch Position 6.
3.
Device is disarmed, acting as a standard exit device which allows free egress.
Resetting device from Bypass Mode to Delayed Egress Mode (Figure 12)
1.
Rotate key counter clockwise, return to center position and remove.
2.
Cover LED is solid RED (default) or LED color setting per the Armed LED Color DIP Switch Position 6.
3.
Device will be in delayed egress mode.
Delayed Egress Operation When Armed
Exit door is normally closed and latched. Delayed Egress device secures door in locked mode with solid red LED (default GREEN
when DIP Switch Position 6 setting is OFF) indicating locked mode status.
Depressing pushpad for (1) one to three (3) seconds or less (depending on DIP Switch position 2 and 3 settings) will sound
device nuisance beeps without initiating alarm.
Depressing pushpad longer than (1) one to three (3) seconds (depending on DIP Switch position 2 and 3 settings) will initiate
an irreversible local audible alarm with a continuous tone, and a visual amber indicator.
After delay time (15 or 30 seconds), device releases, LED changes to green, (default, or red depending on the setting of DIP
Switch position 6), and the local audible alarm remains as a continuous tone until reset by keyswitch.
Remote monitoring contact outputs can be used to alert security personnel. Person depressing pushpad is denied egress for
15 or 30 seconds (depending upon setup) and security personnel are alerted.
NOTE: 30 seconds may be accepted by local jurisdiction.
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without
the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
33
Momentary/
Reset
LHR
Bypass/
Shown
Maintained
Figure 12
FM574 01/23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Corbin russwin ped4000 d series

Table of Contents