Premium Delayed Egress
PED4000 D, PED5000 D Series Exit Device
Installation Instructions
18
Troubleshooting
Problem
Power is applied, but unit will not arm
(No red LED)
Device alarms continuously when power
is applied.
Units with Door Position Switch (made
by other manufacturers)
Device allows mechanical latchbolt
retraction with power applied and LED
shows armed.
Exit device latchbolt/rods will not latch
properly.
LED on rail cover is flashing fast Amber
color (once every 300ms) and rail buzzer
is activated. Door was forced open (DPS
was opened)
LED on rail cover is flashing slow Amber
color (once every 1 sec) and rail buzzer
is activated. Latch bolt was retracted for
10sec.
NOTE: If device is not working properly after troubleshooting, contact your local hardware distributor or
local Corbin Russwin representative, or contact Corbin Russwin.
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without
the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
Solution
• Check all connections on circuit board and wire harness.
• Check for power 24VDC at power inputs (-black) and (+red) and check
polarity.
• Check wire transfer for any bad connections or broken wires.
• Check power output at power supply.
• Must be 24VDC regulated.
• Check pushpad position sensor wire harness on circuit board and all
other connections.
• Check that the position of the pushpad matches the status of the RED
Diagnostic LED (See table on Page 27 for details.).
• Make sure DPS is wired (electrically closed - with door closed) into wire
harness. Make sure DPS is working properly by using a meter to check
continuity when door is opened and closed.
• Check for correct power, 24VDC regulated.
• Check for correct amperage on power supply (must be rated equal or
greater than device, 1A minimum).
• Refer to standard exit device installation instructions troubleshooting
guide.
• Close/secure door, check DPS for proper operation, then reset rail using
cylinder key, or remote rest signal.
• Close/secure door, ensure latch is extended, then reset rail using
cylinder key, or remote rest signal.
35