Premium Delayed Egress
PED4000 D, PED5000 D Series Exit Device
Installation Instructions
12
System Wiring Examples ElectroLynx QC12 Hinge, Continued
11
System Wiring Examples (continued):
Delayed Egress System with Fail Secure Electrofied Exit Trim (ET) and ElectroLynx QC12 Hinge
DEED System with Fail Secure Electrified Exit Trim (ET) and ElectroLynx QC12 Hinge
During a fire alarm condition, the fire alarm contact opens which removes power from DEED (rail), and allows immediate egress.
For External Inhibit (EI) control, a valid code entry at the Inside keypad or valid card presentation at Inside card reader shunts the rail and
allows egress for a time period programmable at the keypad. A valid code entry at the Outside keypad or valid card presentation at
Outside card reader applies power to unlock the Fail Secure ET and allows ingress by turning lever for a time period programmable at the
keypad.
120VAC (L,N,G)
To closed Fire
Alarm Contact
When fire alarm is
activated, contact opens,
disconnects 24VDC to
DEED, allowing
immediate egress
Closeup of end bracket
(with metal tab for P5 Installation)
Connect P5 to this metal
tab on end bracket
QC12 Hinge Pigtail
or
15' Frame Harness
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without
the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
(-)
Securitron
+24VDC
BPS
24VDC
1AMP
Power Supply
Connect Green wire to Earth
Ground (EGND) within BPS Power
Supply or Local Building Ground
Note: Power Supply
24VDC, 2A minimum
per DEED
1 2 3
4 5
6
NO
7
8
9
4291
* 0 #
(Inside)
Keypad
C
Or
Inside Card
Reader Relay
(-)
(by others)
QC12 Hinge
Premium Delayed Egress
Exit Device (DEED)
Door Harness
3" Typical
ElectroLynx pluggable
8-pin and 4-pin
connectors
Note: Wiring to remaining wires is as required
(-)
2, Gray (ET+)
(+)
C
4, Tan (SEC NO)
QC12 Hinge Pigtail
1 2 3
4 5
6
15' Frame Harness
7
8
9
* 0 #
4292
(Outside)
Keypad
-
(
)
Or
Outside Card
Wiring Notes:
Reader Relay
(by others)
(with metal tab for P5 Installation)
Connect P5 to this metal tab on end bracket
5. As another option, instead of wiring to the
External Inhibit (EI) input Orange wire pin 5,
you could move wire to the Remote Reset (RR)
input, White wire pin 3.
(ET+) Red, 2
(ET-) Black, 1
5-pin
connector
Premium 776 (or 774) Fail Secure
Electrified Exit Trim (ET)
From outside of door, route ET wire through
chassis into the opposite side of the LBM wiring,
then plug ET 5-pin connector into mating rail
harness 5-pin connector. Ensure wires are tucked
in, to avoid pinching wires by push bar or chassis
mechanism.
Note: Fail Safe ET
requires different wiring, as
shown on previous page
31
Connect
to QC12
Hinge
or
1. Rail harness, door harness, electric hinge
Closeup of end bracket
and pigtail/frame harness connector
terminations and wire colors all match.
2. Wiring to remaining hinge pigtail wires is as
required. Tape or cap off ends of unused pigtail
wires (not shown) to ensure that they don 't short
to anything.
3. A fire alarm tie-in is required on fire rated
openings.
4. Rail DPS bypass dip switch 8 must be set
ON, which is default setting.
Note that when using RR it will add 5, 10,
20, or 40sec (depending DEED reset delay
dip switch setting) to the keypads/card
RR also can be
readers time setting.
used to rearm DEED from alarm
condition.
FM574 01/23