Premium Delayed Egress
PED4000 D, PED5000 D Series Exit Device
Installation Instructions
18
Troubleshooting, continued
Symptom / Failure
A. Rail won't arm (Green Insert LED won't turn ON / Horn sounds immediately or after a delay)
When trying to arm, the rail goes into alarm immediately after momentary egress times out or after a short delay
after the momentary egress times out.
Are the Yellow, Red, Orange, and Green circuit board Diagnostic LEDs OFF?
YES – Replace defective circuit board.
*NO – All of these LEDs should be OFF. Troubleshoot according to which LED is ON.
If any LED stays ON after troubleshooting according to *, then replace defective circuit board.
B. Rail won't arm(Green Insert LED won't turn ON / Horn stays OFF)
The rail is receiving an external inhibit signal.
The rail is in fire alarm condition.
C. Rail Arms, but will not go into alarm when depressing push bar
Does the Red Diagnostic LED turn ON when depressing push bar?
YES – Replace defective circuit board.
NO – The push rail position sensor is malfunctioning. The rail assembly will need to be replaced.
D. Cover LED fast flashes alternately RED then GREEN every 0.5 seconds (*Hall Error Mode);
Horn/Diagnostic LEDs are off.
The rail may or may not arm prior to this error code.
Check harnesses are connected to the controller PCBs.
Push rail hall switch circuit defective or out of activation range. Consult 1-800-810-WIRE (9473).
If the push bar was in the dogged (retracted) position using a 24 VDC power cycle (via fire alarm/reset or temporary
power outage), this hall error mode will occur. To clear error, un-dog push bar with manual hex key, ensure bar
extends fully then turn cylinder key clockwise to maintained egress position, then counter-clockwiase to Armed
(center) position (or cycle 24 VDC power) to rearm device.
*If horn sounds or flashing sequence differs from the above; or if error mode does not clear,
consult 1-800-810-WIRE (9473).
Important: Rail is not armed when in this condition.
Attention: Electrified Trim applications require a separate raceway and power transfer device. Installation of conductors
or harnesses (by others) through the exit device rail is prohibited as it could lead to product performance issues up to
and including product failure.
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without
the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
36
FM574 01/23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Corbin russwin ped4000 d series

Table of Contents