Premium Delayed Egress
PED4000 D, PED5000 D Series Exit Device
Installation Instructions
1

Panic and Fire Rated Devices

a

Checklist

1. Check device for shipping damage prior to installation and make sure all parts are on hand.
2. Identify options provided with device.
3. Identify model, type and hand of trim if applicable (see exit device and trim instructions for reversing hands).
4. Contact hardware supplier if device is damaged or missing parts.
b
Required Components (Numbered list correlates with numbers in Figure 1)
1. 24VDC UL Listed Regulated and Filtered Power Supply with Fire Alarm Interface (recommend Securitron BPS 24-1 or
24-2 (UL294 Listed), depending on requirements). Power supply is NOT to be used in UL603 Burglar Alarm System.
2. Power transfer UL or ULC listed (8 or 12 wire depending on system) ElectroLynx QC8 or QC12, Securitron (EPT) or
equivalent.
3. Sign (MUST BE INSTALLED ON DOOR ABOVE DEVICE).
NOTE: The delayed egress system is to be installed in accordance with NFPA 101 .
Optional Components (Numbered list correlates with numbers in Figure 1)
c
4. Remote Annunciator
5. Door Position Switch (DPS)
6. Standard Trim
7. Electrified Trim
8. Device and Trim Cylinder
d

Electrical Specifications*

Input Voltage: 24VDC +/- 15% (20.4 - 27.6VDC)
regulated/filtered
Power Consumption @ 24VDC:
 60 - 70 mA (typical) Disarmed
 280 -340 mA (typical) Armed
 320 - 830 mA (typical) Delayed Egress Initiated
 70 - 90 mA (typical when arming)
 Output Relays: Form C, 1 Amp 24VDC
 Operating Temp: -40°C to 66°C (-40°F to 150.8°F)
*Follow Local Electrical Codes for Wiring.
NOTE: Components shown do not reflect all possible applications . Refer to other system wiring diagrams within
this manual . Consult manufacturer for special applications .
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without
the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
6.
5
4.
3
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
6
7
7.
8.
Or
1.
9.
8
4
115 VAC
800 mA
2.
60 Hz
1
Fire
Alarm
Circuit
Req'd
5.
4
3.
2
Figure 1
FM574 01/23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Corbin russwin ped4000 d series

Table of Contents