Premium Delayed Egress
PED4000 D, PED5000 D Series Exit Device
Installation Instructions
11
9
Delayed Egress System with Fire Alarm, Switch Controls, DPS, Horn with ElectroLynx QC8 Hinge
During a fire alarm condition, the fire alarm contact opens which removes power from DEED (rail) and allows immediate egress.
allows egress for a time period programmable at the keypad plus the rail time set by the reset delay dip switch settings. RR also can be
4, Green (EGND)
sends 24VDC to the 4380H remote horn.
120VAC (L,N,G)
Note: The RAR NC contact opens when
DEED is powered, and closes when delayed
egress alarm is initiated
(-)
(+)
+24VDC
When fire alarm is
activated, contact opens,
4380H Horn, or remote alarm, by others
disconnects 24VDC to
DEED, allowing
(-)
immediate egress
DPS Normally Open (NO) contact to
(C) is held electrically closed when
Fire alarm wiring is
magnet is in proximity of switch, when
required on fire rated
the door is closed
openings
On DEED PCBA set DPS Bypass dip
switch 8 to OFF for external DPS use
Wiring Notes:
C
NO
1. Rail harness, door harness, electric hinge
C
NO
and pigtail/frame harness connector
terminations and wire colors all match.
4, Green (EGND)
2. Wiring to remaining hinge pigtail wires is as
required. Tape or cap off ends of unused
pigtail wires (not shown) to ensure that they
don't short to anything.
(-)
3. A fire alarm tie-in is required on fire rated
openings.
(-)
(+)
4380H Horn, or remote alarm, by others
(-)
DPS Normally Open (NO) contact to
(C) is held electrically closed when
magnet is in proximity of switch, when
the door is closed
On DEED PCBA set DPS Bypass dip
switch 8 to OFF for external DPS use
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without
the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
Wiring Notes:
System Wiring Examples ElectroLynx QC8 Hinge, Continued
System Wiring Examples (continued):
DEED system with Fire Alarm, Switch Controls, DPS, Horn with ElectroLynx QC8 Hinge
For External Inhibit (EI) control, a valid code entry at the Inside keypad or valid card presentation at Inside card reader shunts the rail and
allows egress for a time period programmable at the keypad.
For Remote Reset (RR) control, a valid code entry at the Inside keypad or valid card presentation at Inside card reader shunts the rail and
used to rearm rail from alarm condition, with the door closed.
When the rail is armed and the door is forced open, the 3287 door status switch opens and signals the rail sounding the rail alarm.
Connect
When the rail is armed and push bar pressed for time beyond rail nuisance delay dip switch setting, the Remote Alarm Relay (RAR)
to QC8
Hinge
QC8 Hinge Pigtail
or
15' Frame Harness
Securitron
BPS
To closed Fire
24VDC
Alarm Contact
2AMP
Power Supply
Note: Power Supply
24VDC, 2A minimum
per DEED for this
wiring example.
2A allows for
increased load
current due to
addition of electrical
accessories.
Connect
to QC8
Hinge
QC8 Hinge Pigtail
or
15' Frame Harness
Note: The RAR NC contact opens when
QC8 Hinge
DEED is powered, and closes when delayed
egress alarm is initiated
+24VDC
QC8 Hinge Pigtail
or
15' Frame Harness
ElectroLynx pluggable 8-pin
and 4-pin connectors
Only 8-pin connectors need
to be plugged in
(-)
+24VDC
Normally open
switch from card
C
reader, keypad, etc.
C
NO
Connect Green wire to
Earth Ground (EGND)
(-)
within BPS Power Supply or
Local Building Ground
3287
Door Status
Switch,
Or DPS by others
magnet
Premium Delayed Egress
Exit Device (DEED)
Door Harness
3" Typical
29
NO
4, Green (EGND)
Note: The RAR NC contact opens when
DEED is powered, and closes when delayed
egress alarm is initiated
(-)
(+)
+24VDC
4380H Horn, or remote alarm, by others
(-)
DPS Normally Open (NO) contact to
(C) is held electrically closed when
Closeup of end bracket
magnet is in proximity of switch, when
(with metal tab for P5 Installation)
the door is closed
Connect P5 to this metal tab on end bracket
On DEED PCBA set DPS Bypass dip
switch 8 to OFF for external DPS use
Wiring Notes:
1. Rail harness, door harness, electric hinge
and pigtail/frame harness connector
terminations and wire colors all match.
2. Wiring to remaining hinge pigtail wires is as
required. Tape or cap off ends of unused
pigtail wires (not shown) to ensure that they
don't short to anything.
3. A fire alarm tie-in is required on fire rated
openings.
Connect
to QC8
Hinge
QC8 Hinge Pigtail
or
15' Frame Harness
FM574 01/23