Huawei iSitePower-M ISP-M-MAB05B1 Manual page 161

Intelligent power mate
Table of Contents

Advertisement

iSitePower-M V100R002C00
User Manual (MAP05A1, MAB05B1)
7.
8.
9.
Conditions for Judging Overdue Storage
It is recommended that batteries not be stored for a long period. They should be
used soon after being deployed onsite. The batteries should be stored according to
the following requirements.
Table 10-3 Lithium battery recharge interval
Required
Storage
Temperature
–10°C < T ≤
+55°C
1.
2.
3.
4.
Issue 03 (2022-10-28)
The warehouse keeper should collect battery storage information every
month and periodically report the battery inventory information to the
planning department. The batteries that have been stored for nearly 15
months (at –10°C to +25°C), 9 months (at 25°C–35°C), or 6 months (at 35°C–
55°C) should be recharged in a timely manner.
Batteries should be delivered based on the "first in, first out" rule.
After the battery production test is complete and before the batteries are
stored, the batteries must be recharged to at least 50% of the SOC.
Actual Storage
Temperature
T ≤ –10°C
–10°C < T ≤ +25°C
25°C < T ≤ 35°C
35°C < T ≤ 55°C
T > 55°C
Dispose of deformed, damaged, or leaking batteries directly irrespective of
how long they have been stored.
The storage duration starts from the latest charge time labeled on the battery
package. If a battery is qualified after recharge, update the latest charge time
on the label (next recharge time = latest charge time + recharge interval).
The longest power storage period of a battery is three years. A battery can be
recharged at most for three times within the three years. For example, it can
be recharged every 8 months or every 12 months. It is recommended that
batteries be scrapped if the longest storage period and maximum recharging
times are exceeded.
If a lithium battery is stored for a long time, capacity loss may occur. After a
lithium battery is stored for 12 months at the recommended storage
temperature, the irreversible capacity loss rate is 3%–10%. If customers
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 System Maintenance
Recharge
Interval
Not allowed
15 months
9 months
6 months
Not allowed
Remarks
Within the
recommended
storage duration:
Use the batteries
as soon as
possible.
Reaching the time
for recharge:
Recharge the
batteries.
The total storage
duration should
not exceed the
warranty period.