Huawei iSitePower-M ISP-M-MAB05B1 Manual page 74

Intelligent power mate
Table of Contents

Advertisement

iSitePower-M V100R002C00
User Manual (MAP05A1, MAB05B1)
No.
One End
3
Ground
point
4
Ground
point
Table 7-6 Cables in parallel system scenario
No.
One End
1
Ground
point
2
AC parallel
box
3
AC parallel
box
4
AC parallel
box
5
AC parallel
box
6
AC parallel
box
Issue 03 (2022-10-28)
Other End
Type
Ground bar
Outdoor single-core
copper cable
(customer
side)
Ground point
Outdoor single-core
on the
copper cable
module for
capacity
expansion
Other End
Type
Ground bar
Outdoor single-core
copper cable
(customer
side)
PDB
Outdoor three-core copper
cable (L/N/PE)
(customer
side)
AC output
Outdoor three-core copper
cable (L/N/PE)
AC input
Outdoor three-core copper
cable (L/N/PE)
PDC
Outdoor three-core copper
cable (L/N/PE)
(customer
side)
Ground bar
Outdoor single-core
copper cable
(customer
side)
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Preparing Cables
Recommended
Specifications
Main ground cable: 4–6
2
mm
(same as the cross-
sectional area of the AC
input power cable)
Main ground cable: 6 mm
Recommended
Specifications
Main ground cable: 4–6
2
mm
(same as the cross-
sectional area of the AC
input power cable)
● Conductor cross-
sectional area: 25 mm
● Cable outer diameter:
16–26 mm
● Conductor cross-
sectional area: 4–6 mm
● Cable outer diameter:
13.7–16.9 mm
● Conductor cross-
sectional area: 4–6 mm
● Cable outer diameter:
13.7–16.9 mm
● Conductor cross-
sectional area: 25 mm
● Cable outer diameter:
16–26 mm
● Conductor cross-
sectional area: 25 mm
● Cable outer diameter: 8–
11 mm
2
2
2
2
2
2
63

Advertisement

Table of Contents
loading

This manual is also suitable for:

Isitepower-m isp-m-map05a1