8.2.5.4 Installing Communications Cables in a Parallel System

● When installing communications cables in a parallel system, install build-out
● The length of a single communications cable cannot exceed 3 m.
● The method of installing communications cables between power modules is the
Procedure
Step 1 Install communications cables between parallel power modules.
Figure 8-23 Installing communications cables
(1) Build-out resistor
Step 2 Connect the FE ports of the master and slave devices using a network cable.
Issue 03 (2022-10-28)
NO TICE
resistors at the first and last modules. The build-out resistors are delivered with
the product.
same as that between battery modules.