iSitePower-M V100R002C00
User Manual (MAP05A1, MAB05B1)
Figure 4-11 Setting DOD to Start
Parameter
DOD to Start
Schedule Mode
Minimum Charge
Duration
Issue 03 (2022-10-28)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Set the battery depth of
discharge at which the
genset is started and the
batteries stop
discharging. The default
value is 60.
Set the genset
scheduling mode. The
default mode is Cycle
Mode.
Tradition Mode: The
genset is started when
the grid power fails and
is shut down when the
grid power is normal.
Cycle Mode: The genset
startup/shutdown
control logic is executed
in cycle mode. The
genset is started when
DOD to Start is reached.
No Control Mode: The
genset startup/shutdown
is performed manually.
Set the minimum charge
time. The default value is
0.
4 Application Scenarios
Value Range
5–90
Tradition Mode
Cycle Mode
No Control Mode
0–2880