Danfoss Turbocor TT Series Service Manual page 93

Twin-turbine centrifugal series compressors
Hide thumbs Also See for Turbocor TT Series:
Table of Contents

Advertisement

 19.  Position the wires as shown inFigure 4-67   M otor Wire Position and Figure 4-68   I GV Motor Wires 
Figure 4-67 Motor Wire Position
 
Figure 4-68 IGV Motor Wires Connected
 20.  Install the Feedthrough using the four (4) M5x16 fasteners and install the IGV Motor Cable Retainer Clip 
Figure 4-69 Feedthrough Orientation
 21.  If available, test the motor operation with a stepper motor driver. Operation of the IGV can also be 
 22.  Clean the mating surfaces of both the compressor and IGV.
 23.  Clean, lubricate, and install the IGV Housing O-ring.
Connected.
under one of the fasteners. Tighten only three (3) of the fasteners to 5Nm (44 in.lb.) while leaving the 
fourth fastener with the retainer clip slightly loose. Refer to Figure 4-69   F eedthrough Orientation.
tested using the SMT driving the IGV manually (once the IGV has been mounted on the compressor).
M-SV-001-EN Rev. H-1/23/2023 Page 93 of 294