Compressor Status
Trigger Method
Description
 
Table 5-7 Compressor Status 2 Faults
Compressor Status 2
Trigger
Description
Method
Suction Pressure 
RFT
Sensor Fault
Discharge 
RFT
Pressure Sensor 
Fault
Suction 
RFT
Temperature 
Sensor Fault
Discharge 
RFT
Temperature 
Sensor Fault
Inverter 
RFT
Temperature 
Sensor Fault
Cavity 
RFT
Temperature 
Sensor Fault
Soft Start 
RFT
Temperature 
Sensor Fault
Invalid Bearing 
INS
Calibration Fault
Inverter Cooling 
AFT
Control Fault
Motor Cooling 
AFT
Control Fault
 
 
Troubleshooting
 
Review the fault log for actual suction pressure and temperature, entering air/water 
l
temperature (if available) and other conditions that are recorded at the time of fault.
 
Verify suction pressure/temperature sensor. Refer to Section 4.32.3  
l
Pressure/Temperature Sensor Verification on page 246.
Troubleshooting
 
Sensor errors occur when the sensor is providing a reading that is outside the normal readable 
l
temperature range and therefore must have an error in the reading or functional problem with the 
sensor
 
Verify the associated sensor and related connections
l
 
Sensor errors occur when the sensor is providing a reading that is outside the normal readable 
l
temperature range and therefore must have an error in the reading or functional problem with the 
sensor
 
Verify the associated sensor and related connections
l
 
Sensor errors occur when the sensor is providing a reading that is outside the normal readable 
l
temperature range and therefore must have an error in the reading or functional problem with the 
sensor
 
Verify the associated sensor and related connections
l
 
Sensor errors occur when the sensor is providing a reading that is outside the normal readable 
l
temperature range and therefore must have an error in the reading or functional problem with the 
sensor
 
Verify the associated sensor and related connections
l
 
Sensor errors occur when the sensor is providing a reading that is outside the normal readable 
l
temperature range and therefore must have an error in the reading or functional problem with the 
sensor
 
Verify the associated sensor and related connections
l
 
Sensor errors occur when the sensor is providing a reading that is outside the normal readable 
l
temperature range and therefore must have an error in the reading or functional problem with the 
sensor.
 
Verify the associated sensor and related connections
l
 
Sensor errors occur when the sensor is providing a reading that is outside the normal readable 
l
temperature range and therefore must have an error in the reading or functional problem with the 
sensor.
 
Verify the associated sensor and related connections
l
 
If a bearing calibration is not saved in the EEPROM, this fault will be triggered, a valid calibration is 
l
required prior to the compressor accepting demand.
 
Calibrate the compressor bearings using the Calibration Tool and save to EEPROM. Cycle power and 
l
verify the calibration is retained in EEPROM.
 
Refer to Table 5-6   C ompressor Status on page 255 regarding High Inverter Temperature Fault 
l
Troubleshooting
 
Refer to Table 5-6   C ompressor Status on page 255 regarding High Cavity Temperature Fault 
l
Troubleshooting
M-SV-001-EN Rev. H-1/23/2023 Page 259 of 294