Danfoss Turbocor TT Series Service Manual page 289

Twin-turbine centrifugal series compressors
Hide thumbs Also See for Turbocor TT Series:
Table of Contents

Advertisement

Component
Test Point
 
Solenoid Actuators
 
Stator Resistance
 
 
Stator Thermistor 
Resistance
F4 & F5
4.8 W
9.3 W
Phase 1:2
Phase 1:3
Phase 2:3
+ to -
Expected Value
Verification Section
Fuses
30-38Ω
4.14.2.2   V erifying Soft Start 
Fuses
108Ω – 132Ω
4.6.3   S olenoid Verification
56.25Ω – 68.75Ω
4.6.3   S olenoid Verification
>0.0Ω and <1Ω
4.23.4.2   S tator Resistance 
Verification
>0.0Ω and <1Ω
4.23.4.2   S tator Resistance 
Verification
>0.0Ω and <1Ω
4.23.4.2   S tator Resistance 
Verification
150-300Ω at 70° 
4.23.4.2   S tator Resistance 
F (21°C)
Verification
M-SV-001-EN Rev. H-1/23/2023 Page 289 of 294
Measured
Value
 
 
 
 
 
 
 

Advertisement

Table of Contents
loading