Figure 4-131 DC-DC Connectors (Potted)
 6.  If the DC-DC Converter is the potted style, remove the J7 connector from the Soft Start. Refer to Figure 
TT/TG compressors utilizing the open frame DC-DC design do not utilize the Closed-Top Soft Start J7: Trigger Signal connector.
 
 7.  Remove the Soft Start AC/DC Harness from the Softstart.
 
Figure 4-132 Closed-Top Soft Start J1 and J7 Removal
 
4-132   C losed-Top Soft Start J1 and J7 Removal for this and the following step.
 a.  For compressors with the Closed-Top Soft Start, remove the J1 and J7 (if equipped) connector. 
Refer to Figure 4-132   C losed-Top Soft Start J1 and J7 Removal.
 b.  For compressors with the Open-Top Soft Start, remove connectors J1 and J8. Refer to Figure 4-133  
Open-Top Soft Start J1 and J8 Removal on page 136.
NOTE
M-SV-001-EN Rev. H-1/23/2023 Page 135 of 294