The set screw may be difficult to release as it will have threadlocker applied. For proper engagement into the set screw, do not use a ball-
end hex wrench.
 
Figure 4-56 IGV Motor Assembly Removal
 7.  Slide the Locking Collar Tool (P/N 100246) into the housing and over the worm shaft. Ensure the drive 
Figure 4-57 Locking Collar Tool
 8.  Turn the Locking Collar clockwise to remove. Refer to Figure 4-58   L ocking Collar .
Figure 4-58 Locking Collar
The Locking Collar contains a left-hand thread. To remove, turn clockwise when viewing from the motor end.
 9.  Remove the worm gear by rotating the IGV Throat clockwise by hand or rotate the worm shaft by hand. 
 
Page 88 of 294 - M-SV-001-EN Rev. H 1/23/2023
pins are engaged in the Locking Collar. Refer to Figure 4-57   L ocking Collar Tool.
Refer to Figure 4-59   W orm Gear Removal on page 89.