Danfoss Turbocor TT Series Service Manual page 257

Twin-turbine centrifugal series compressors
Hide thumbs Also See for Turbocor TT Series:
Table of Contents

Advertisement

Compressor Status
Trigger Method
Description
Low Leaving Fluid 
DFT
Temperature Fault
High Pressure Ratio 
AFT
Fault
Bearing/Motor Fault 
INS
Active
Sensor Fault
RFT
High SCR 
AFT
Temperature Fault
Troubleshooting
faults.
Recommendation:
 
Ensure the liquid motor-cooling line has sufficient liquid supply and is not blocked.
l
 
Prevent prolonged operation at a pressure ratio less than 1.5.
l
 
o
Low Lift operation requires additional considerations, refer to Applications 
Manual
 
Verify the solenoids are operational and not blocked. Refer to Section 4.6.3   S olenoid 
l
Verification on page 73.
 
Verify the solenoid actuators. Refer to Section 4.6.3   S olenoid Verification on page 73.
l
 
Verify the Serial Driver. Refer to Section 4.26.3   S erial Driver Verification on page 217.
l
 
Verify cavity temperature sensor. Refer to Section 4.31.3     C avity Temperature Sensor 
l
Verification on page 242.
 
(Removed from CC 4.X.X software)
l
 
Suggests insufficient evaporator fluid flow or insufficient system load.
l
 
Check evaporator fluid flow and system load.
l
 
Verify leaving fluid temperature sensor.
l
 
Ensure LEAVE jumper is installed on the I/O board.
l
 
Review the fault log for entering and leaving air/water temperature (if available) and 
l
other conditions that are recorded at the time of fault.
 
Suggests the condenser ressure is high, not enough load on the evaporator, or 
l
insufficient water/air flow in either condenser or evaporator.
 
Check the electronic expansion valve (EXV) operation, condenser, evaporator loads, and 
l
water/air flow.
 
Review the fault log for suction and discharge pressures and other conditions that are 
l
recorded at the time of fault.
 
If a Motor Fault type or a Bearing Fault type is present, the Bearing/Motor Fault is 
l
triggered.
 
This is not an actual fault, only an indication that a fault has occurred in the Motor or 
l
Bearing section. Refer to Table 5-8   M otor/System Status on page 260 and Table 5-5  
Bearing Fault Types on page 254.
 
Review fault log for indication of values out of specified ranges recorded at time of fault. 
l
Verify the questionable sensor and related connections for failure.
 
Inverter temperature: The sensor embedded in the Inverter requires a replacement of 
l
the Inverter if determined faulty.
 
Cavity Temperature: Refer to Section 4.31.3     C avity Temperature Sensor Verification on 
l
page 242.
 
Suction Temperature: Verify suction pressure/temperature sensor. Refer to Section 4.32.3  
l
Pressure/Temperature Sensor Verification on page 246.
 
Discharge Temperature: Verify discharge pressure/temperature sensor. Refer to Section 
l
4.32.3   P ressure/Temperature Sensor Verification on page 246.
 
Leaving Water Temperature: Verify LEAVE jumper is installed on I/O board.
l
 
Suction Pressure: Review fault log for recorded value.
l
 
Discharge Pressure: Review fault log for recorded value.
l
Removed from CC 4.2.X and later software
 
Indicates the SCR cooling is insufficient.
l
 
If this fault occurs three times within a 30-minute period, a Lock-Out Fault will occur.
l
M-SV-001-EN Rev. H-1/23/2023 Page 257 of 294