Danfoss Turbocor TT Series Service Manual page 262

Twin-turbine centrifugal series compressors
Hide thumbs Also See for Turbocor TT Series:
Table of Contents

Advertisement

Motor/System
Trigger
Status Description
Method
Generator Mode 
DFT
Active
EEPROM 
INS
Checksum Fault
SCR Ripple 
AFT
Voltage Fault
 
Page 262 of 294 - M-SV-001-EN Rev. H 1/23/2023
Troubleshooting
 
Compare the Back EMF value to the displayed readings in the Compressor Monitor Tool and Fault 
l
and Event Log details to determine conditions related to the fault.
 
Permanent damage to Back EMF can be caused by insufficient motor cooling, repeated overheating 
l
of cavity, faulty Inverter, faulty BMCC, repeated Rotor Starting Torque or Single phase Over-Current 
faults. Refer to  Inverter Error on page 260.
 
Verify the Inverter. Refer to Section 4.22.2   I nverter Verification on page 176.
l
 
Verify the Stator. Refer to Section 4.23.4   M otor Verification on page 195.
l
 
Indicates, at greater than 0 RPM, the measured actual DC Bus voltage has fallen below the Generator 
l
Mode Enabled Level value. Also, could be electronic "noise" when no actual drop in voltage has 
occurred.
 
Measure the incoming main AC voltage.
l
 
Measure the DC bus voltage using the DC Bus Test Harness.
l
 
Compare the measured voltages to the displayed readings in the Compressor Monitor Tool and Fault 
l
and Event Log details to determine conditions related to the fault.
 
Typically, this fault is recorded when power to the compressor is removed while it is running.
l
 
Indicates there is an error reading the EEPROM in the BMCC.
l
 
Perform a bearing calibration and save to EEPROM, cycle the power.
l
 
If the error is still present, the BMCC must be replaced.
l
 
Suggests that a voltage or current imbalance may exist between the incoming AC phases to the 
l
SCRs.
 
Measure the difference in current and voltage between the AC phases.
l
 
If there is a current imbalance (more than 5%) between the phases, verify the incoming AC power 
l
supply.
 
Review the Compressor Monitor Tool for SCR Voltage Ripple readings at the time of the fault.
l
 
Phase imbalance can also be caused by a faulty SCR, SCR Gate, Gate control from the Soft Start 
l
Board, or a faulty power capacitor.
 
Verify the SCRs. Refer to Section 4.18.2   S CR Verification on page 142.
l
 
Verify the Soft Start Board. Refer to Section 4.14.2   S oft Start Verification on page 115.
l

Advertisement

Table of Contents
loading

Table of Contents