AK-CC55 Multi Coil
Function
Description
Fan control during
Fan operation during defrost Here you can set how
defrost
the fan is to operate during defrost.
0: Stopped (runs during pump down)
1: Running (stopped during "fan delay)
2: Running during pump down and defrost. After that
stopped
3: Running during pump down and defrost until de-
frost stop sensor reaches fan stop temperature limit
Fan start delay
Delay of fan start after defrost. Here you set the time
that is to elapse from compressor start after a defrost
and until the fan may start again. (The time when re-
maining water is transformed into ice on the evapora-
tor).
Fan start tempera-
Temperature limit for starting the fans after a defrost.
ture
When the measured S5 evaporator temperature is
getting below the set limit, the fans are started
Fan stop tempera-
If the fan control during defrost has been set up for it,
ture
the fans can be stopped during the defrost if the de-
frost sensor exceeds the set temperature limit
Rail heat during de-
Define how rail heat is controlled during defrost
frost
0: Rail heat is OFF all the time
1: Rail heat is ON all the time
2: Normal rail heat control
Display delay after
Set the maximum time the display should show the
defrost
defrost code "-d-" after a defrost. The normal temper-
ature readout is normally started when the tempera-
ture in the case is OK again or if a high temperature
alarm is raised.

Defrost schedules

Table 34: Defrost schedules
Function
Description
Defrost schedule
Def. start 1 - Hours
Time in hours for start of defrost
Def. start 1 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Def. start 2 - Hours
Time in hours for start of defrost
Def. start 2 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Def. start 3 - Hours
Time in hours for start of defrost
Def. start 3 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Def. start 4 - Hours
Time in hours for start of defrost
Def. start 4 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Def. start 5 - Hours
Time in hours for start of defrost
Def. start 5 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Def. start 6 - Hours
Time in hours for start of defrost
Def. start 6 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Monday - Follow
schedule
Tuesday - Follow
schedule
Wednesday - Follow
schedule
Thursday - Follow
schedule
Friday - Follow
schedule
Saturday - Follow
schedule
Sunday - Follow
schedule
© Danfoss | Climate Solutions | 2022.08
Values
0=OFF, 1=ON, 2=OFF at drip, 3=OFF at high temp
0=OFF, 1=ON, 2=Normal control
Values
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
Code
Short name
d09
d09 FanDuringDef
d07
d07 FanStartDel
d08
d08 FanStartTemp
d41
d41 Def Fan Stop
d27
d27 Railh.at def
d40
d40 Disp. d del.
Code
Short name
t00
t00 Def.Schedule
t01
t01 Def. 1 hr.
t11
t11 Def. 1 min.
t02
t02 Def. 2 hr.
t12
t12 Def. 2 min.
t03
t03 Def. 3 hr.
t13
t13 Def. 3 min.
t04
t04 Def. 4 hr.
t14
t14 Def. 4 min.
t05
t05 Def. 5 hr.
t15
t15 Def. 5 min.
t06
t06 Def. 6 hr.
t16
t16 Def. 6 min.
t51
t51 Mon.Schedule
t52
t52 Tue.Schedule
t53
t53 Wed.Schedule
t54
t54 Thu.Schedule
t55
t55 Fri.Schedule
t56
t56 Sat.Schedule
t57
t57 Sun.Schedule