Humidity Control - Danfoss AK-CC55 Multi Coil User Manual

Case/room controller (eev)
Hide thumbs Also See for AK-CC55 Multi Coil:
Table of Contents

Advertisement

AK-CC55 Multi Coil

Humidity control

Table 29: Humidity control
Function
Description
Control state A
Readout of the actual control state of the controller
Control state B
Readout of the actual control state of the controller
Control state C
Readout of the actual control state of the controller
Humidity sensor
Humidifier
Actual status of output function
Dehumidifier
Actual status of output function
Humidity control
Select the type of humidity control
Humidity cut-in
Set-point for the humidity control.
At humidifier control, the humidifier is started when
the humidity has dropped to the set-point.
At dehumidifier control, the dehumidifier is stopped,
when the humidity has dropped to the set-point
Humidity differen-
Differential for humidity control.
tial
At humidifier control, the humidifier is stopped when
the humidity has increased with the set differential
above the set-point.
At dehumidifier control, the dehumidifier is started,
when the humidity has increased with the set differ-
ential above the set-point
Humidity high alarm
High alarm limit for relative humidity
limit
Humidity low alarm
Low alarm limit for relative humidity
limit
Humidity alarm de-
Delay of high and low humidity alarms
lay
Humidity sensor -
Min signal
Humidity sensor -
Max signal
Humidity ctrl. at de-
Select how to control humidity during defrost:
frost
No: Humidity control is stopped during defrost
Yes: Normal humidity control is running during de-
frost
Humidity max.
Maximum limit for thermostat air temperature in or-
temp.
der for humidity control to run (frost limit)
Humidity min. temp. Minimum limit for thermostat air temperature in or-
der for humidity control to run (frost limit)
© Danfoss | Climate Solutions | 2022.08
Values
0=Normal ctrl., 1=Hold after defrost, 4=Drip off,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
0=Normal ctrl., 1=Hold after defrost, 4=Drip off,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
0=Normal ctrl., 1=Hold after defrost, 4=Drip off,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
0=OFF, 1=ON
0=OFF, 1=ON
0=None, 1=Humidifier, 2=Dehumidifier
0=No, 1=Yes
Code
Short name
u00
u00 Ctrl. state
U74
U74 Ctrl.State B
U83
U83 Ctrl.State C
U57
U57 RH level %
U58
U58 Humidifier
U96
U96 Dehumidifier
h31
h31 RH function
h23
h23 RH Cutin SP
h24
h24 RH Diff.
h25
h25 RH HighLimAl
h26
h26 RH LowLimAl
h27
h27 RH Al. delay
h29
h29 RH Min Value
h30
h30 RH Max Value
h28
h28 RH CtrlAtDef
h32
h32 RH Max temp.
h33
h33 RH Min temp.
BC365022028193en-000201 | 46