Danfoss AK-CC55 Multi Coil User Manual page 45

Case/room controller (eev)
Hide thumbs Also See for AK-CC55 Multi Coil:
Table of Contents

Advertisement

AK-CC55 Multi Coil
Function
Description
Alarm air temp. B
Measured temperature for alarm thermostat
Alarm air temp. C
Measured temperature for alarm thermostat
High alarm limit
Readout of actual high alarm limit for the tempera-
ture monitoring
Low alarm limit
Readout of actual low alarm limit for the temperature
monitoring
S4 Air OFF evap. A
Actual sensor value
S4 Air OFF evap. B
Actual sensor value
S4 Air OFF evap. C
Actual sensor value
Reset alarms
Command for resetting all alarms, unless they are still
active
High alarm limit 1
Upper alarm limit. The limit value is set in absolute
value. The limit value will be raised with the night off-
set during night operation.
Low alarm limit 1
Lower alarm limit. The limit value is set in absolute
value
High alarm limit 2
Upper alarm limit. The limit value is set in absolute
value. The limit value will be raised with the night off-
set during night operation.
Low alarm limit 2
Lower alarm limit. The limit value is set in absolute
value
Alarm delay A
Alarm delay (short alarm delay on air temperature). If
the upper or the lower alarm limit values are excee-
ded, a timer function will commence. The alarm will
not become active until the set time delay has been
passed. The time delay is set in minutes
Alarm delay pull-
Alarm delay at tempeature pull down conditions
down A
(long alarm delay). This time delay is used during
start-up, during defrost and immediately after a de-
frost. There will be a change-over to the normal time
delay when the temperature has dropped below the
set upper alarm limit.
Door open alarm
Time delay for door alarm
delay
Door restart inj. de-
Start of refrigeration when the door is open. If the
lay
door has been left open, refrigeration will be started
after the set time.
Alarm delay DI 1
Time delay for digital input alarm
Alarm delay DI 2
Time delay for digital input alarm
© Danfoss | Climate Solutions | 2022.08
Values
0=OFF, 1=ON
Code
Short name
U34
U34 Alarm air B
U92
U92 Alarm air C
y10
--- High al. lim
y11
--- Low al. lim
u16
u16 S4 air temp.
U76
U76 S4 temp B
U85
U85 S4 temp C
x15
--- Reset alarm
A13
A13 HighLim Air
A14
A14 LowLim Air
A20
A20 HighLim2 Air
A21
A21 LowLim2 Air
A03
A03 Alarm delay
A12
A12 Pulldown del
A04
A04 DoorOpen del
o89
o89 DoorInjStart
A27
A27 Al.Delay DI1
A28
A28 Al.Delay DI2
BC365022028193en-000201 | 45