Defrost Schedules - Danfoss AK-CC55 Water Loop User Manual

Case controller for semi plug-in
Hide thumbs Also See for AK-CC55 Water Loop:
Table of Contents

Advertisement

AK-CC55 Water Loop
Function
Description
Time staggering
Time staggering for defrost cut-ins during start-up
power-up
The function is only relevant if you have several refrig-
eration appliances or groups where you want the de-
frost to be staggered in relation to one another. The
function is furthermore only relevant if you have
chosen defrost with interval start. The function delays
the interval time by the set number of minutes, but it
only does it once, and this at the very first defrost tak-
ing place when voltage is connected to the controller.
The function will be active after each and every pow-
er failure.
Max. thermostat run
Defrost on demand. Aggregate refrigeration time set
time
here is the refrigeration time allowed without de-
frosts. If the time is passed, a defrost will be started.
With setting = 0 the function is not in use.
Drip off time
Here you set the time that is to elapse from a defrost
and until the compressor is to start again. (The time
when water drips off the evaporator).
Max. hold time
Max. standby time after coordinated defrost. When a
controller has completed a defrost it will wait for a
signal tellingthat the refrigeration may be resumed. If
this signal fails to appear for one reason or another,
the controller itself will start the refrigeration when
the standby time has elapsed.
Fan control during
Fan operation during defrost Here you can set how
defrost
the fan is to operate during defrost.0: Stopped (runs
during pump down)1: Running (stopped during "fan
delay)2: Running during pump down and defrost. Af-
ter that stopped3: Running during pump down and
defrost until defrost stop sensor reaches fan stop tem-
perature limit
Fan start delay
Delay of fan start after defrost. Here you set the time
that is to elapse from compressor start after a defrost
and until the fan may start again. (The time when re-
maining water is transformed into ice on the evapora-
tor).
Fan start tempera-
Temperature limit for starting the fans after a defrost.
ture
When the measured S5 evaporator temperature is
getting below the set limit, the fans are started
Fan stop tempera-
If the fan control during defrost has been set up for it,
ture
the fans can be stopped during the defrost if the de-
frost sensor exceeds the set temperature limit
Rail heat during de-
Define how rail heat is controlled during defrost0: Rail
frost
heat is OFF all the time1: Rail heat is ON all the time2:
Normal rail heat control
Display delay after
Set the maximum time the display should show the
defrost
defrost code "-d-" after a defrost. The normal temper-
ature readout is normally started when the tempera-
ture in the case is OK again or if a high temperature
alarm is raised.

Defrost schedules

Table 24: Defrost schedules
Function
Description
Defrost schedule
Def. start 1 - Hours
Time in hours for start of defrost
Def. start 1 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Def. start 2 - Hours
Time in hours for start of defrost
Def. start 2 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Def. start 3 - Hours
Time in hours for start of defrost
Def. start 3 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Def. start 4 - Hours
Time in hours for start of defrost
Def. start 4 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Def. start 5 - Hours
Time in hours for start of defrost
Def. start 5 - Minutes Time in minutes for when defrost cycle is to be star-
ted
© Danfoss | Climate Solutions | 2022.04
Values
0=OFF, 1=ON, 2=OFF at drip, 3=OFF at high temp
0=OFF, 1=ON, 2=Normal control
Values
0=No, 1=Yes
Code
Short name
d05
d05 Time stagg.
d18
d18 MaxTherRunT.
d06
d06 DripOff time
o16
o16 MaxHoldTime
d09
d09 FanDuringDef
d07
d07 FanStartDel
d08
d08 FanStartTemp
d41
d41 Def Fan Stop
d27
d27 Railh.at def
d40
d40 Disp. d del.
Code
Short name
t00
t00 Def.Schedule
t01
t01 Def. 1 hr.
t11
t11 Def. 1 min.
t02
t02 Def. 2 hr.
t12
t12 Def. 2 min.
t03
t03 Def. 3 hr.
t13
t13 Def. 3 min.
t04
t04 Def. 4 hr.
t14
t14 Def. 4 min.
t05
t05 Def. 5 hr.
t15
t15 Def. 5 min.
BC378540472015en-000101 | 53

Advertisement

Table of Contents
loading

Table of Contents